Hotels that recycle greywater have mostly done one thing: collected shower and bath water from guest rooms, treated it biologically or with filtration, disinfected it, and piped it back to flush the same building’s toilets. The documented installations show the technology can run for years without guest complaints, and between them they show the problems an owner has to manage: separate piping that is hard to add to an existing building, equipment failures that showed up as odor in the toilets, storage sized for more water than guests actually used, and a steady load of inspection and testing.

This article walks through the installations that agencies and universities have published in enough detail to learn from: a German hotel that flushed 221 rooms with treated shower water, a Spanish resort hotel used as a European Union test site, a Colorado residence hall pilot that logged every failure, and the hotel laundries that already reuse their own water. It then maps those lessons onto US code requirements and onto an existing hotel’s numbers. Every installation described here comes from the report cited; Maredes had no role in any of them.

What the documented installations have in common

The record is thinner than the topic’s reputation suggests. Much of what a search turns up is marketing or design studies; the table below lists installations described by an agency, a public research program or a university, with what each source reports.

BuildingWater reused and whereTreatment describedReported by
Four-star hotel, Offenbach, Germany; 380 bedsBath and shower water to toilets in 221 guest rooms; designed for 20 cubic meters (about 5,300 gallons) a daySettling, six-stage rotating biological contactor, UV with an optical sensorGTZ ecosan data sheet, 2006
Three-star resort hotel, Lloret de Mar, Spain; 441 roomsRoom shower water to room toilets (existing system); pilot treatment lines for greywater, wastewater and pool waterSeveral pilot technologies, including a membrane bioreactorEuropean Commission CORDIS, DEMEAUMED project, 2014 to 2017
University residence hall, Fort Collins, Colorado; 14 first-floor roomsShower and sink water to student toiletsCoarse filters, chlorine dosing, blue dye, online chlorine monitoringColorado State University thesis, 2014
Hotel laundry, Seattle; two hotels' linensLaundry wash and rinse water back to the washersLint removal, pressure filters, oxidizer, UV and ozone disinfectionPNNL for the Department of Energy, 2014
Hotel laundry, San Antonio; 473 roomsFinal rinse reused as the next load's first washNone described; simple recyclingEPA WaterSense profile, 2014
Sources: GTZ ecosan data sheet 018 (2006); CORDIS DEMEAUMED final report summary (2017); Vandegrift, Colorado State University (2014); PNNL-23535 (2014); EPA WaterSense Westin Riverwalk profile (2014). All checked November 2026. Conversions to US units are ours.

The list is short on purpose. Several hotel examples that circulate online exist only as trade articles, company pages or design proposals, and one well-known US hotel report could not be loaded at its published address. They are left out because there was no primary report to check them against.

Three patterns run through the table. The one large toilet-flushing system with a known history went in while the hotel was still under construction, and the Colorado pilot served just 14 rooms of an existing building. Laundry water reuse, which stays inside one room of the building, comes with the clearest published economics. And every report that covers operation spends as much space on maintenance and monitoring as on the treatment itself.

A German hotel that flushed 221 rooms with shower water

The best-documented hotel system is the one at the ArabellaSheraton Am Büsing Palais in Offenbach, near Frankfurt, described in a data sheet published in 2006 by GTZ, the German government’s technical cooperation agency. The data sheet reports ten years of operation since January 1996. It does not say whether the system still runs today, and neither does this article.

What was built

The system was not in the original plans. According to GTZ, the idea came up during construction of the 380-bed, four-star hotel, so the treatment plant was built in the garage, on two parking spaces. It takes about 35 square meters, roughly 380 square feet.

Only bath and shower water was collected. The wash basins sat on the opposite side of each bathroom from the tubs and showers, and adding drain pipes for them was not worth it, because bath and shower water alone was enough to flush the toilets. Water from wash basins and other sources went to the city sewer as usual.

The treatment train, as the data sheet describes it:

  1. Bath and shower water drains to settling tanks.
  2. After settling, it flows continuously through a six-stage rotating biological contactor, where bacteria growing on turning plastic carriers consume the degradable pollutants.
  3. Surplus sludge settles out and is discharged to the sewer every three months.
  4. The treated water passes UV disinfection. An optical sensor checks the UV, and if it detects a disturbance, the water goes to the sewer instead of the service water tank.
  5. Disinfected water is stored in a service water tank and pumped through a separate network to the toilets of 221 guest rooms.
  6. When the service tank runs short, it refills automatically with drinking water. When it is full, incoming greywater bypasses treatment and goes straight to the sewer.
Bath and shower drains Settling tanks Six-stage biological contactor UV with optical sensor Service water tank Toilets in 221 guest rooms City sewer (sludge every 3 months) Drinking water top-up UV fault: to sewer Tank full: greywater bypasses to sewer Tank low
Solid lines: normal flow. Dashed lines: fail-safe and overflow paths. Source: GTZ ecosan data sheet 018, Greywater recycling in Hotel ArabellaSheraton, Offenbach (November 2006), checked November 2026. Simplified; tank sizes and pumps omitted.

Sizing, quality and money

GTZ reports the plant was designed for 20 cubic meters a day, for 400 beds. The designers assumed 70 to 90 liters of greywater per person per day (about 18 to 24 gallons) and 50 to 70 liters of flushing water per overnight stay (about 13 to 18 gallons), so supply comfortably exceeded demand.

Germany had no legal minimum quality for recycled greywater at the time, so the design followed a leaflet from the Berlin Senate Department. The data sheet’s table shows the effluent below every criterion: total coliforms under 0.1 per milliliter against a limit of 100, E. coli under 0.03 against 10, and a 7-day biochemical oxygen demand under 3 milligrams per liter against 5.

The money, in 2006 euros: a total investment of about 170,000 euros, of which the treatment system was 72,000 and the rest was extra piping, construction, planning and design. Savings were put at about 5,000 cubic meters of drinking water a year (about 1.3 million gallons), worth about 30,000 euros at Offenbach’s business price of about 6 euros per cubic meter including wastewater fees. Annual operation and maintenance was about 3,900 to 4,000 euros.

What broke, and what the staff did

The data sheet is frank about failures. The first primary settling tanks, bought as rainwater storage tanks made of recycled polyethylene, cracked after some time in service and were replaced with new polyethylene tanks. The two motors driving the biological contactors were replaced because they could not regulate rotation speed. The first rotor of one contactor broke under the unbalanced weight of wet bacteria and was repaired.

Routine care was modest but never zero. One staff member spent about half an hour each week checking the color, thickness and structure of the biomass, the network for leaks, tank levels and odors. Staff handled quarterly maintenance, and the equipment provider did annual maintenance. GTZ reports the treated water was odorless and clear, and that, according to the hotel, no guest complained.

What a US hotel can take from Offenbach

  • Collect only what you need. Leaving out the wash basins saved drain piping without starving the toilets.
  • Find space early. A plant for a few hundred guests fit on two parking spaces, but only because the garage was there to use.
  • Build the bypasses in. Surplus greywater went to the sewer and a UV fault diverted water away from the toilets, so the plant could fail without guests noticing.
  • Treat the top-up as a cross-connection. The drinking water refill to the service tank is exactly the connection US plumbing code requires to be protected, by an air gap or a backflow assembly.
  • Expect sludge. The biological process produced sludge that had to be removed every three months.

A Spanish resort hotel used as an EU test site

The second documented hotel is the Hotel Samba, a 441-room, three-star hotel in Lloret de Mar, Catalonia, which hosted the European Union’s DEMEAUMED research project from January 2014 to June 2017. The final report summary on CORDIS, the European Commission’s research results service, is useful less for the pilot equipment than for what it found in a working hotel.

What the hotel already had

Before the project began, almost every use in the hotel ran on drinking water. The one exception, the report notes, was a greywater system that sent room shower water to flush the toilets in the hotel rooms. Tap water use ranged from about 1,500 to 5,000 cubic meters a month with the season, roughly 400,000 to 1.3 million gallons, highest for the rooms, the kitchen, the pool and the basement.

What its greywater looked like

The project measured each water stream. Shower greywater showed limited daily and weekly variation, medium organic content (chemical oxygen demand about 200 milligrams per liter, biochemical oxygen demand about 160), suspended solids about 50, traces of some pharmaceuticals, and some microbiological contamination. Laundry effluent was much stronger, with chemical oxygen demand up to 1,500 milligrams per liter. Kitchen effluent varied widely through the day and week.

That split matters for any hotel. Shower water is the easiest greywater to treat; laundry water carries far more organic load; kitchen water is excluded from greywater under the EPA and Department of Energy definitions cited later in this article anyway.

What the rules required in Spain

Spain’s reuse regulation, RD 1620/2007, applied to the site. The report summarizes it this way: toilet flushing with reclaimed water is authorized only if every section up to the point of use is a marked dual circuit, and E. coli and turbidity must be monitored twice a week, suspended solids weekly and helminth eggs every two weeks. That is a far heavier testing schedule than most US hotel engineers would expect.

What the project concluded

According to the European Commission’s summary of results, a combination of the tested technologies could let a hotel save 30 to 50 percent of its tap water, but closing the water cycle completely at the Hotel Samba was not possible for technical reasons and because of EU-wide restrictions on reusing certain types of water. The final report adds a caution about money: low water prices in most EU countries make returns on reuse technologies long, and economic savings “may be more questionable” than water savings.

The pilot equipment itself was tested at demonstration scale on the hotel’s greywater, including a membrane bioreactor, a plant-based living wall and a solar photoelectro-Fenton oxidation unit. Combined in a single treatment line, the Commission’s summary reports, the technologies removed 95 percent of conductivity, 97 percent of suspended solids, 89 percent of organic content and 71 percent of nitrogen, along with several pharmaceutical and endocrine-disrupting compounds. Those are pilot results under research supervision, not the performance of a packaged unit.

A survey within the project gathered data from 73 hotels in the Euro-Mediterranean region. Most monitored water only at the whole-facility level, the most common saving measure was water-saving showers, 30 percent had no saving measures at all, and most had not separated greywater from blackwater.

A residence hall pilot that logged every failure

No US hotel greywater system has been published in comparable operating detail in the sources we could load. The closest US record comes from a lodging-like building: Aspen Residence Hall at Colorado State University, where a pilot system flushed student toilets with treated shower and sink water. Jillian Vandegrift’s 2014 master’s thesis documents its first semester of real use.

The system

The pilot collected greywater from 14 first-floor rooms into a 300-gallon storage tank sized for a 24-hour residence time. Water passed coarse filters, received a measured dose of sodium hypochlorite, sat in a 65-gallon disinfection tank designed for a one-hour contact time, and was dyed blue before a booster pump sent it to the toilets. A backflow preventer protected the drinking water supply, and the Colorado State Plumbing Board approved the pilot by variance after an inspection and code updates.

The control logic is the part a hotel should study. An online analyzer held chlorine residual in the disinfection tank between 1 and 5 milligrams per liter. At 1.5 or 4 milligrams per liter, an alarm told the assigned plumber to adjust the dose. At 1 or 5, a latching alarm cut power to the treatment system and switched the toilets to city water.

What went wrong in one semester

The system ran in full operation from February 7 to May 5, 2014. The thesis lists the incidents:

Date What happened Cause found
February 13 A student’s shower would not drain The coarse filter before the storage tank clogged with hair and debris; it was removed
Early operation Erratic chlorine readings Fats, oils and grease coated the chlorine probe membrane; frequent rinsing was added to the procedures
March 12 Foul odor in toilets A broken pump tube stopped chlorine dosing; the alarm switched to city water, but treated water sitting in the pipes lost its residual
April 11 Foul odor in toilets The chlorine pickup tube had slipped above the liquid in the chemical tank
April 17 Disinfection tank pumped dry A breaker failure cut power to part of the system
May 2 Black water in the test toilet tank, odor complaints Likely stagnant water released from the pressure tank or debris from the pump

The storage tank turned out to be oversized. The design assumed up to 28 students; the real maximum was 25, only 17 opted in, and the system processed an average of 91 gallons a day against a design of 300. The thesis notes that older, stagnant greywater in the tank could turn septic and recommends a smaller tank.

The thesis also records what the team planned to change: a chlorine probe with a higher measuring range, so the system could run at a higher residual without hitting the low alarm, priced at $1,905; a smaller 160-gallon storage tank raised on a platform; and weekly residual checks in student toilets by an experienced tester. A second 300-gallon tank had been left unused for future laundry effluent.

Student surveys were mixed. Of the participants, 11 found the water in their toilets displeasing at least sometimes, and every one of them pointed to odor. Three were very satisfied and two were very unsatisfied and would not take part again. The survey found no illness that students linked to the greywater.

Why a hotel should care

A residence hall is not a hotel, but the lessons transfer directly. The failures were ordinary: a filter, a pump tube, a breaker. The fail-safe to city water worked, yet guests would still have smelled the toilets, because water already in the pipes lost its chlorine. And occupancy below the design figure created the very stagnation the design tried to avoid.

Laundry water: the greywater hotels already reuse

EPA’s WaterSense at Work defines gray water as wastewater from lavatory sinks, laundries and bathing, never from toilets or urinals and excluding kitchen sinks. By that definition, hotels that recycle laundry water are already reusing greywater, and they are the best-documented US examples.

The Department of Energy’s demonstration at the Grand Hyatt Seattle, reported by PNNL in 2014, measured a system that filtered, disinfected and reheated laundry discharge for reuse in the washers. It saved an average of 365,000 gallons a month. At the Westin Riverwalk in San Antonio, EPA reports a simple last-rinse, first-wash reclaim that added a 20 percent cut on top of new washers. Neither project needed a second piping network through the guest floors, because the water never leaves the laundry.

A Colorado State University feasibility study in the same thesis shows why. It examined a 254-room, eight-floor hotel in Fort Collins that runs near full occupancy. Retrofitting all eight floors to collect shower water was judged too complicated and costly. Sending laundry effluent to subsurface or drip irrigation on about an acre of grounds was estimated to cut the hotel’s water use by up to 6 percent a year, and 11 percent a month in the growing season. As hypothetical scenarios, shower water to toilets would save about 7 percent, and laundry plus shower water would meet all flushing demand and save about 8 percent.

The comparison between ozone and recycling for hotel laundries, with the federal measurements, is set out in a separate article on this journal’s hotels and apartments page.

Seven lessons that repeat across the record

Read side by side, the reports agree on more than they differ. These seven lessons come up again and again.

1. Separate piping decides the project

Every toilet-flushing system in the record had separate greywater drains and a separate service water network. The Offenbach hotel added them during construction; the Fort Collins hotel study rejected a retrofit of eight floors as too costly. The Department of Energy’s FEMP guidance says graywater systems in existing buildings require retrofitting the plumbing and should be considered when constructing new buildings, because dual plumbing can be integrated into the design with less labor.

2. Size to the flushing you will actually have

The Offenbach plant was sized for 400 beds and a generous per-guest supply, and it simply bypassed surplus greywater to the sewer. The Colorado pilot was sized for full occupancy and ran at under a third of design flow, which left water sitting in the tank. A hotel at 60 percent occupancy in January and 95 percent in October needs storage and controls that cope with both.

3. Fail safe to city water, and plan for the water in the pipes

Both the Offenbach and Colorado systems topped up or switched over to drinking water automatically, and both sent bad water away from the toilets rather than into them. The Colorado record adds the subtle part: switching sources does not fix water already in the distribution pipes. A flush-out routine after any alarm is part of the design.

4. Testing is a real, recurring cost

Spain’s rules required E. coli and turbidity tests twice a week for toilet-flushing reuse. A 2025 study by Pimentel-Rodrigues and Silva-Afonso in Frontiers in Environmental Science lists the tests a Portuguese technical specification requires in operation: monthly E. coli, enterococci, pH, BOD, suspended solids, turbidity and ammonia; twice-yearly Legionella (with a mandatory summer sample), Pseudomonas aeruginosa, total nitrogen and phosphorus; and monthly residual chlorine where chlorine is used. The authors write that greywater reuse may carry health risks especially in buildings for collective use, such as student residences and hotels, and that analytical control is often ignored or undervalued.

Cost scales badly at small sizes. For the single-family house the Frontiers authors analyzed, the required tests would cost no less than 1,200 euros a year in Portugal, against a mains water bill under 500 euros. A hotel spreads the same kind of testing over far more water, though the authors also caution that in buildings with significant health risks, such as hospitals and nursing homes, the testing required can make greywater a poor economic choice.

5. Guests notice odor first

The Offenbach hotel reported no guest complaints with clear, odorless water. In Colorado, every student who found the toilet water displeasing blamed odor, and each odor episode traced to a dosing or equipment failure. Color matters too: the Colorado pilot dyed its treated water blue before it reached the toilets. For a hotel, a single bad-smelling toilet can become a review.

6. Parts wear, and someone has to own them

Cracked tanks, replaced motors and a broken rotor in Germany; a clogged filter, a broken pump tube and a fouled probe in Colorado. None of these is exotic. What they share is that someone on staff had to notice, diagnose and fix them, on a schedule and with spare parts on hand.

7. Plan for replacement, not just operation

The Frontiers study notes that the main components of a greywater system have a useful life of 15 to 20 years, against 40 to 50 years for a rainwater system. A hotel that plans a greywater plant should budget for replacing it within the life of the building, and say so in the business case.

Matching supply to flushing demand in a US hotel

The arithmetic of supply and demand is the easy part, and in a hotel it almost always shows more greywater than toilets need. The greywater calculator runs it for any building.

Example (fictional). The Pearlbank Hotel, a fictional 96-room select-service hotel, averages about 134 guests a day at 70 percent occupancy. With planning assumptions of 16 gallons of shower and bath water and 3 gallons of bathroom sink water per guest per day, and 10 percent lost in treatment, the calculator shows about 2,291 gallons of greywater collected and treated a day. Five flushes per guest at 1.28 gallons need about 858 gallons a day, so greywater could cover all of it, with about 1,434 gallons a day left over for the sewer and about 313,024 gallons a year of city water saved. Storage for one day of flushing demand would be about 858 gallons. Even so, the hotel’s review screened greywater out: the existing building has no separate drain and supply piping, and adding it would mean opening walls and ceilings across the guest floors. The planned design uses laundry rinse recycling and a rain and condensate tank instead; the example project explains why. Every number is a planning assumption.

That example captures the usual result for an existing hotel. Supply is not the constraint; pipes are. The questions that decide feasibility are where the bathroom drains run, whether shower and toilet drains can be separated at a reachable point, how a second supply line can reach every toilet, and where a treatment skid and tanks can sit.

For a new hotel or a gut renovation, those questions change completely. The Offenbach data sheet shows the treatment equipment fitting on two parking spaces, and the piping, construction and planning, about 100,000 of the 170,000 euros, were the larger part of the investment even when added during construction.

Whether the numbers pay, at your water and sewer rates, energy prices and testing costs, is a separate calculation. It is covered in is greywater recycling worth it.

What US codes and standards ask for

The rules in the United States are set locally, but they draw on the same few documents. This section describes what those documents say; the building official and health department for your property decide what applies.

The plumbing code

ICC’s 2018 IPC Code Essentials summarize the International Plumbing Code’s nonpotable water chapter for graywater:

  • Graywater cannot be stored untreated for more than 24 hours.
  • Graywater used to flush water closets and urinals must be treated by an on-site treatment system that complies with NSF 350.
  • The code sets minimum requirements for residual disinfection and filtering, and local laws may add initial or ongoing testing, perhaps by an approved testing agency.
  • Nonpotable outlets need signage, distribution systems need labeling, and storage tanks must be identified as nonpotable.
  • Potable make-up connections must be protected; a physical air gap is the best protection, and where a physical connection is needed, a reduced pressure principle backflow prevention assembly is appropriate.

The same pages add a warning worth repeating: even though these systems are addressed in the code, they may not be approved for use locally. The section-by-section detail is in greywater and plumbing codes.

NSF/ANSI 350 Class C

NSF/ANSI 350 covers onsite residential and commercial water reuse treatment systems. On NSF’s listing current as of November 21, 2026, Class C means multifamily residential units and commercial facilities, and Class R means single-family dwellings. The listing covers 69 products from six manufacturers, most of them wastewater systems.

Greywater products, listed as laundry and bathing, are few. Class C greywater units from two manufacturers appear, with rated capacities from 79 to 7,926 gallons a day. Hotel-scale greywater treatment that carries the certification the code names is therefore available, but the field is narrow, and the listed rated capacity, not a brochure, is what to size against. When Maredes specifies greywater treatment, it names a unit listed under NSF/ANSI 350 in the class that fits the building, where the market offers one.

Disinfection and piping

EPA’s WaterSense at Work recommends disinfection for pathogens for all water used indoors for toilet flushing, says treated gray water should be used within 24 hours, and advises consulting local health department officials first and checking with fixture manufacturers about warranties. FEMP adds that graywater systems should be installed under local plumbing codes by professional, licensed plumbing contractors, with color-coded dual plumbing, and that local requirements may include inspection after installation and backflow preventers.

In Mississippi

Mississippi is not among the 12 states EPA lists as having regulations or guidelines for onsite non-potable reuse, according to EPA’s onsite reuse resources page, last updated June 26, 2026. In practice that means approval runs project by project through the local building official and, where wastewater is involved, the health department. Every Maredes reuse design includes a written code path memo that names the approving offices, the code edition, backflow protection, labeling and monitoring.

What monitoring and staffing a hotel takes on

A hotel greywater system adds a small utility plant to the building, with its own rounds and records. The schedule below gathers the tasks the documented systems actually performed. It is a starting point for a written plan, not a substitute for what the local authority and the equipment maker require.

Frequency Task Where it comes from
Continuous Disinfection check with automatic diversion or switch to city water on a fault Offenbach UV sensor; Colorado chlorine analyzer and latching alarms
Daily Glance at alarms, tank levels and the treated water’s color and smell Colorado incidents; Offenbach weekly checks
Weekly About half an hour: biomass condition, leaks, tank levels, odors Offenbach data sheet
Weekly or more Rinse or clean sensors exposed to greywater Colorado chlorine probe fouling
Twice weekly to monthly Laboratory tests for E. coli, turbidity and other parameters, as the authority requires Spain’s RD 1620/2007 as summarized by CORDIS; Portuguese specification in the Frontiers study
Quarterly Planned maintenance by staff; sludge removal where the process makes it Offenbach data sheet
Twice yearly Legionella sample, including one in summer, where required Portuguese specification in the Frontiers study
Yearly Service by the equipment provider; review of logs and test results Offenbach data sheet
After any alarm Flush treated water out of the distribution piping before switching back Colorado odor incidents

Two things make this schedule work. The first is a named owner, usually the chief engineer, with a backup. The second is a maintenance log that records every reading, test and repair, so the next person can see what normal looks like. The monitoring and service page describes how Maredes structures this for systems it designs.

Any greywater loop also belongs inside the building’s water management program for Legionella. The Legionella checklist is a place to start, and the standards page lists the certifications and safety rules Maredes specifies against.

When greywater fits a hotel, and when to start elsewhere

Greywater for toilet flushing is the most ambitious reuse a hotel can attempt, and the record says it fits a narrow set of buildings well. Use this table as a first screen.

Situation Greywater for toilets Usually better first
New hotel, piping still on paper Strong candidate; plumb dual drains and supply from the start Design efficiency and laundry reuse alongside it
Gut renovation that opens every bathroom wall Possible; price the piping first Compare with condensate and laundry reuse
Existing hotel, walls closed Weak; piping cost dominates Leaks, fixtures, laundry rinse recycling, condensate
Large on-premise laundry Laundry water is the easier greywater Laundry recycling inside the laundry
Humid climate with air handlers or a cooling tower Secondary Condensate to cooling tower make-up or irrigation
No staff to own a treatment plant Weak Simpler sources with less monitoring

The humid-climate row deserves a word for Gulf South hotels. FEMP notes that a large amount of condensate forms on cooling coils in areas with hot, humid summers such as the southeastern United States, and that it is well suited to cooling tower make-up. EPA reports that one Atlanta hotel sends about 1 million gallons of air handler condensate a year to its towers. Condensate needs less treatment than greywater and no second network through the guest floors.

Efficiency still comes before any of it. The Frontiers study calls efficient devices the priority measure, citing studies in Portugal that point to about a 30 percent reduction in existing buildings from fixture changes alone. The order of work for a hotel, from leaks to reuse, is collected in this journal’s hotels and apartments section. For how a treated greywater flushing loop is put together, component by component, see greywater toilet flushing.

What to do before you commit

If greywater is on the table for your hotel, these steps turn the lessons above into decisions you can defend.

  1. Measure flushing demand, not just greywater supply. Count toilets, flush volumes and occupied room-nights by month, and run the greywater calculator at your lowest and highest occupancy.
  2. Trace the drains. Get the plumbing drawings, or open a ceiling on one guest floor, and find where shower, lavatory and toilet drains join.
  3. Price the piping separately from the equipment. In the Offenbach project, piping and related work cost more than the treatment plant.
  4. Ask for NSF/ANSI 350 Class C listings for any treatment unit proposed, and check the listed rated capacity on NSF’s site.
  5. Ask the building official and health department early what they will require for approval, testing and reporting.
  6. Write the monitoring plan before the bid, with a named owner, test schedule, alarm responses and a log.
  7. Plan the guest side: dyed water if required or chosen, signage on non-potable outlets in service areas, and a response script for an odor complaint.
  8. Compare simpler sources such as condensate and laundry rinse water, which the record shows are easier to run.

Questions for an equipment supplier

  • Is the unit listed under NSF/ANSI 350 Class C for laundry and bathing water, and at what rated capacity?
  • Where is a comparable unit operating, and can you share its maintenance log and test results, not just a reference contact?
  • What happens on each failure: power loss, low disinfectant, sensor fault, pump failure, high level?
  • How is disinfectant residual measured, and how often must sensors be cleaned or calibrated?
  • How does the system behave at 40 percent occupancy, and how long does water sit in storage then?
  • What sludge or concentrate does it produce, and where does it go?
  • What spare parts should be kept on site, and what is the annual service cost?
  • How much electricity does it use per 1,000 gallons treated?

A Maredes water review runs this screen for a hotel, from the bills and drawings to a monthly water balance and a reuse recommendation that may well say not to use greywater. The greywater recycling page explains how a system is designed when it does fit, and the hotels page covers the rest of a lodging property.

Have a building in mind?

If this article describes a question about your home, property or business, tell us about the building. A project starts with a water review and a written summary of what we found.