Standards Maredes specifies, and what we do not claim
Standards here are requirements Maredes places on equipment and on the work. They are not certifications of Maredes, which holds none.
For: Owners, builders, engineers and officials reviewing a Maredes specification

Every Maredes design names the standards its equipment and its work must meet. This page lists them, with the public source for each. They are requirements written into a specification and checked against the certifier’s listing. Maredes itself holds no certifications, licenses or memberships: certified laboratories test the water, licensed contractors install, and a licensed engineer seals drawings where the local authority requires it.
Drinking water treatment units
Each component is specified by the NSF/ANSI standard that matches the claim it must meet. The titles below are the ones NSF uses in its listings.
| Standard | Listing title | Where Maredes specifies it |
|---|---|---|
| NSF/ANSI 42 | Drinking Water Treatment Units, Aesthetic Effects | Carbon for chlorine, chloramine, taste and odor; sediment filters with a particulate claim |
| NSF/ANSI 44 | Cation Exchange Water Softeners | Softeners, only when a hardness result justifies one |
| NSF/ANSI 53 | Drinking Water Treatment Units, Health Effects | Filters with a listed claim such as lead, cyst, or PFOA and PFOS reduction |
| NSF/ANSI 55 | Ultraviolet Microbiological Water Treatment Systems | UV units, with the listed class (A or B) and a rated flow at least equal to the design flow |
| NSF/ANSI 58 | Reverse Osmosis Drinking Water Treatment Systems | Reverse osmosis at a tap, with the specific chemical claims the test calls for |
| NSF/ANSI 62 | Drinking Water Distillation Systems | Distillers, where a result calls for one |
| NSF/ANSI 401 | Drinking Water Treatment Units, Emerging Compounds/Incidental Contaminants | Units with a listed claim for an incidental compound found in the test |
Certification is claim-specific. A filter listed under NSF/ANSI 53 for lead reduction is not certified for every contaminant the standard covers, so each line of a specification names the claim. EPA lists five ANSI-accredited certification bodies for home filters: CSA Group, IAPMO R&T, NSF, UL and WQA. Its April 2024 filter fact sheet also cautions that PFAS certifications focus on PFOA and PFOS and “do not yet indicate that a filter will remove PFAS down to the levels EPA has now set.”
Plumbing components: lead-free marks
Under Section 1417 of the Safe Drinking Water Act, “lead free” means a weighted average of 0.25 percent lead across the wetted surfaces of pipes, fittings and fixtures, and 0.2 percent for solder and flux. EPA says that since September 21, 2023, importers and manufacturers must certify that these products meet the requirement, and that an NSF/ANSI/CAN 372 mark indicates compliance; an NSF/ANSI/CAN 61 mark (“Drinking Water System Components, Health Effects”) indicates the same and that the product met leachate requirements. Maredes specifies components that carry one of these two marks. The marks describe the components, not the water.
Reuse treatment units: NSF/ANSI 350
NSF lists greywater and wastewater reuse systems under “Onsite Residential and Commercial Water Reuse Treatment” (NSF/ANSI 350). EPA’s WaterSense at Work explains that greywater systems can be evaluated for bathing water only, laundry water only, or both. The listing uses two classes: Class R for single family residential dwellings and Class C for multi-family residential units and commercial facilities. On November 21, 2026 it named six manufacturers, three of them with greywater systems. Maredes specifies a listed unit in the class that fits the building where the market offers one. Where none applies, as with laundry rinse recycling or rainwater, the specification states the treatment steps and the water quality checks instead.
EPA drinking water limits
National Primary Drinking Water Regulations are legally enforceable for public water systems. Secondary standards are non-mandatory guidelines for taste, odor and appearance. A private well is not regulated under the Safe Drinking Water Act, so its owner decides what to test. A short selection:
| Contaminant | EPA value | Type |
|---|---|---|
| Lead | 0.015 mg/L (15 ppb); 0.010 mg/L from November 1, 2027; health goal zero | Action level (treatment technique) |
| Copper | 1.3 mg/L | Action level |
| Nitrate (as nitrogen) | 10 mg/L | Maximum contaminant level |
| Arsenic | 0.010 mg/L | Maximum contaminant level |
| Total coliforms | Goal zero; no more than 5.0 percent of a system’s monthly samples positive | Indicator of other bacteria (Revised Total Coliform Rule) |
| PFOA and PFOS | 4.0 parts per trillion each (2024 rule); on May 18, 2026 EPA proposed keeping these limits and letting systems request two more years, to 2031 | Maximum contaminant level |
| Iron | 0.3 mg/L | Secondary |
| Manganese | 0.05 mg/L | Secondary |
| pH | 6.5 to 8.5 | Secondary |
| Total dissolved solids | 500 mg/L | Secondary |
The water test reader compares your own results with these values. It is a screening tool, not medical advice; ask your utility, the laboratory or MSDH about a result.
Cross-connection and backflow
A cross-connection is any point where non-potable water could reach drinking water piping. In a reuse system that point is the make-up connection, where city or well water tops up a tank. Every Maredes reuse design puts an air gap or a backflow preventer on each make-up connection, chosen for the hazard and to the local plumbing code and the water utility’s rules. The DOE notes that local requirements may include backflow preventers. Where the code or the utility requires periodic testing of a device, the service plan schedules it.
Purple pipe and signage
The DOE says dual plumbing should be color coded and that reclaimed water pipes “must be color coded with purple tags or tape according to standards set by the American Water Works Association.” Maredes specifies purple pipe or purple tape and tags along every reuse line, and signs at each fixture or hose bib supplied with reuse water saying that the water is non-potable. Reuse water is never connected to a drinking fountain, sink, shower or ice machine.
Legionella and building water management
The CDC says that “an effective water management program is the primary strategy to control Legionella growth and spread.” Its toolkit asks owners to assess the need for a program in buildings such as those with multiple housing units and a centralized hot water system, buildings of more than 10 stories, and buildings with a cooling tower, hot tub or decorative fountain. It sets out seven steps, from naming a team to documenting the program, and cites ASHRAE 188, “Legionellosis: Risk Management for Building Water Systems.” Reuse adds tanks and stored water, so every Maredes reuse design includes a section for the building’s water management program team. Maredes does not claim compliance with or certification to ASHRAE 188. The Legionella checklist is a starting point.
Codes and approval in Mississippi
The 2021 International Plumbing Code has a chapter titled “Chapter 13 Nonpotable Water Systems”. Which edition applies to a building is a local question. The ICC says Mississippi adopts codes through the Mississippi Building Code Council; coastal counties must adopt and enforce the state building code, and elsewhere “enforcement is voluntary but encouraged.” ICC-NTA reported that Mississippi adopted the 2024 I-Codes, including the 2024 International Plumbing Code, for modular construction as of July 1, 2026.
No Mississippi rule on greywater or onsite reuse was found. EPA lists 12 states with onsite non-potable reuse regulations or guidelines, and Mississippi is not one of them. A text search of MSDH’s on-site wastewater regulations and the 2018 on-site wastewater law found no greywater or reuse provisions. Approval is therefore project by project, with the local building official and, where wastewater is involved, the health department. The code path memo in every reuse design records who decides and on what basis. This page describes public sources; it is not legal advice, and local rules apply.
What Maredes does not claim
Maredes is not a certified laboratory, a licensed contractor, plumber or engineer, and it holds no certification or membership from NSF, WQA, IAPMO, UL or any other body. It does not claim that any design is approved, code-compliant or permitted until the local authority says so, and it never designs reuse for drinking.
Sources
Every page below was loaded and read on 2026-11-22.
- EPA: National Primary Drinking Water Regulations, checked 2026-11-22
- EPA: Revised Total Coliform Rule, checked 2026-11-22
- EPA: PFAS National Primary Drinking Water Regulation, checked 2026-11-22
- EPA: Secondary drinking water standards, checked 2026-11-22
- EPA: Private drinking water wells, checked 2026-11-22
- EPA: Home water filter fact sheet, PFAS (April 2024), checked 2026-11-22
- EPA: Use of lead free pipes, fittings, fixtures, solder and flux, checked 2026-11-22
- EPA: How to identify lead free certification marks (June 2024), checked 2026-11-22
- NSF: Drinking water treatment unit listings, including the NSF/ANSI 42, 53 and 55 listing pages, checked 2026-11-22
- NSF: NSF/ANSI/CAN 61 listings, checked 2026-11-22
- NSF: Wastewater listings and the NSF/ANSI 350 listing, checked 2026-11-22
- EPA WaterSense at Work, Section 8: Onsite alternative water sources, checked 2026-11-22
- DOE FEMP: Best Management Practice 14, alternative water sources, checked 2026-11-22
- CDC: Legionella control toolkit, worksheet and program steps, checked 2026-11-22
- ICC: 2021 International Plumbing Code, Chapter 13 (title only), checked 2026-11-22
- ICC: Mississippi code adoption and ICC-NTA: Mississippi adopts new I-Codes, checked 2026-11-22
- EPA: Onsite non-potable water reuse resources, checked 2026-11-22
- MSDH: On-Site Wastewater Regulations and the 2018 on-site wastewater law, checked 2026-11-22
Start with a water review.
Tell us about the building: what it is, who uses it, where the water comes from and what you would like to change. We reply with questions and a time to walk the building with you.