Legionella water management checklist
CDC calls an effective water management program the primary strategy to control Legionella. This checklist follows the program's parts, step by step.
For: Managers of hotels, apartment buildings, clinics and senior housing, and owners adding reuse

Checklist
Legionella bacteria grow in building water systems where water sits, stays warm and loses its disinfectant, and they spread when that water is sprayed into the air from showers, cooling towers, hot tubs and fountains. CDC’s toolkit states that “an effective water management program is the primary strategy to control Legionella growth and spread.” This checklist follows the parts of such a program. It is for managers of hotels, apartment buildings, clinics and senior housing, and for owners adding a reuse system, which brings new tanks and pipes into the building.
The checklist is a way to see what is in place and what is missing. It is not a program, it does not certify anything, and it is not medical or legal advice. Maredes does not claim compliance with ASHRAE 188, the standard CDC cites, or with any other program requirement. Tick items as you confirm them, then print or download the list; nothing is saved when you leave the page.
Team and scope
CDC’s first step is to establish a water management program team; its second is to describe the building water systems. The checklist adds one named person responsible for the program.
Start by checking whether the building needs a program. CDC’s worksheet asks whether the building is a healthcare facility with overnight patients, primarily houses people older than 65, has “multiple housing units and a centralized hot water system,” or has “more than 10 stories (including basement levels).” It also asks about devices: a cooling tower, a hot tub that is not drained between uses, a decorative fountain, a centrally installed mister, atomizer, air washer or humidifier. Hotels and apartment buildings served by a central water heater answer yes to the housing and hot water question.
The diagram item asks for every water system on one page: supply, heaters, storage, risers, cooling towers, fountains, hot tubs and any reuse system.
Where Legionella can grow
CDC’s third step is to identify areas where Legionella could grow and spread. EPA’s drinking water regulations note that Legionella “multiplies in heating systems.” The checklist asks for four lists:
- Stagnant water: unused rooms and floors, dead legs left from old renovations, storage tanks and reuse tanks.
- Temperature in the growth range: lukewarm stretches of hot water piping, storage held too cool, cold lines warmed by nearby heat.
- Low disinfectant: far ends of the system and anything fed from storage.
- Spray: showers, cooling towers, fountains, hot tubs and misters.
Reuse water belongs on these lists. EPA WaterSense at Work notes that air-conditioning condensate “can grow bacteria” and recommends disinfection for all water used indoors, such as for toilet flushing.
Control measures
CDC’s fourth step is to decide where to apply control measures and how to monitor them, and the fifth is to establish interventions when control limits are not met. In practice, each place on the lists above gets a control limit (a temperature, a disinfectant residual or a flushing interval) and a way to check it. Unoccupied rooms and low-use outlets are flushed on a schedule; water heaters and storage stay at their set temperatures; reuse and rainwater systems have their own disinfection and monitoring. The building’s water management team sets the actual limits.
Monitoring and response
CDC’s sixth and seventh steps are to make sure the program runs as designed and is effective, and to document and communicate all the activities. That means readings on a set schedule, written down; a written response for each reading outside its limit; and reviews. CDC describes a program as requiring continuous review and updating when necessary. The checklist suggests reviewing at least once a year and after renovations, water outages or a case of disease, as a practical minimum.
Reuse systems and the program
A reuse system adds exactly the features this checklist looks for: tanks where water waits, pipes that run only when toilets flush or irrigation starts, and treatment that must keep working. A Maredes reuse design describes the tanks, piping, disinfection and monitoring points so the building’s team can add them to its program. Storage sizing is on the tank sizing calculator, readings belong in the filter maintenance log, and standards explains what Maredes specifies for reuse water. For ongoing readings and sampling, see monitoring and service.
Start with a water review.
Tell us about the building: what it is, who uses it, where the water comes from and what you would like to change. We reply with questions and a time to walk the building with you.