Is AC condensate water safe to reuse? What it can supply in a building

The reader questionIs air-conditioning condensate safe to collect and reuse, and what can a building in a humid climate use it for?

A cold green glass bottle beaded with condensation stands half in the water, drops running down its dry upper half into the clear water around it.

Air-conditioning condensate can be reused for non-potable jobs such as cooling tower make-up, drip irrigation and, after filtration and disinfection, toilet flushing. It is not drinking water, and it is not clean just because it starts as vapor: an EPA study of 13 air handling units, completed in July 2026, found the potential for microbial growth and metals leaching in untreated condensate and said collection systems should be managed like other building water systems. In a humid climate like Jackson’s, a building makes the most condensate from May through September, the same months its cooling tower and landscape need the most water.

Below: what condensate picks up, how much a building makes, which uses need which treatment, Legionella and metals, what the water is worth on a Jackson bill, and who approves a system. Volumes follow the site’s condensate calculator, and dollar figures the water savings calculator.

What AC condensate is and why it is low in minerals

AC condensate is the water that forms on an air conditioner’s cooling coil when warm, humid air passes over it and cools below its dew point. It is a byproduct every cooling system already makes, and in most buildings it goes down the drain.

The Department of Energy’s Federal Energy Management Program (FEMP) describes condensate forming on the coils of “packaged or rooftop units, dedicated outdoor air units, and air handling units,” and notes that “a large amount of condensate can form on cooling coils in areas with hot, humid summers such as the southeastern United States” (FEMP, Best Management Practice 14). The water drips into a drain pan and leaves through a condensate line.

EPA’s WaterSense at Work guide says it is most often “discharged to the sewer system” (EPA WaterSense at Work, Section 8). Collecting it means intercepting that line.

Because the water comes out of the air rather than the ground, it carries almost no dissolved rock. EPA’s table of onsite alternative sources rates air handling condensate a low concern for sediment, total dissolved solids (TDS, the minerals and salts dissolved in water), hardness and organic load, and a medium concern for pathogens. It adds one note: condensate “may contain copper when coil cleaned.” FEMP says condensate “starts off very pure with a very low dissolved mineral content.”

The San Antonio Water System (SAWS), which published a condensate manual for commercial buildings in 2013, adds two details that matter for design (SAWS, Condensate Collection and Use Manual). Condensate forms “in the same manner as distilled water,” with a slightly acidic pH of about 5.8 and no minerals. Being slightly acidic, it “tends to react with materials with which it comes in contact.” It also collects whatever the air carried onto the coil, including microorganisms drawn in from outdoors or from the occupied space.

Property What the sources say What it means for reuse
Minerals and TDS Low concern (EPA); “very low dissolved mineral content” (FEMP) Little scale, which suits cooling towers
pH Slightly acidic, about 5.8 (SAWS) Can dissolve metal from coils, pans and pipes
Metals Copper possible after coil cleaning (EPA); metals leaching in untreated collections (EPA, 2026) Keep coil cleaning water out; limit bare metal where the use is sensitive
Microbes Medium concern; can grow bacteria from building air (EPA) Disinfect before uses people touch or breathe; keep storage short
Timing Highest volumes during high cooling loads (EPA) Supply peaks in summer, with cooling and irrigation demand

Is AC condensate safe to drink or reuse?

Condensate is not drinking water, and none of the federal or utility guidance reviewed here treats it as one. It is a non-potable source that suits some reuse jobs with little treatment and others only after filtration and disinfection. Whether a use is acceptable depends on how much people touch, breathe or swallow the water.

FEMP defines non-potable water as water that “has not been treated to standards safe for human consumption, but is useful for specific end uses such as irrigation, dust suppression, toilet and urinal flushing, or make-up water for mechanical equipment” (FEMP, Alternative Water Treatment Levels). Treating any alternative source to drinking water standards brings Safe Drinking Water Act requirements and a certified operator, FEMP notes. Maredes does not design potable reuse of any kind.

What EPA’s 2026 study found

EPA’s National Water Reuse Action Plan Action 4.5, completed in July 2026, set out to close a gap: condensate is “generally considered a high-quality source,” but “empirical studies of condensate water quality to inform appropriate risk management practices have been limited” (EPA, WRAP Action 4.5 summary). The action team, which included EPA researchers, ASHRAE and IAPMO, characterized condensate from 13 air handling units in North Carolina, Indiana, Texas and Florida. It focused on contaminants relevant to cooling towers and irrigation.

The result, in EPA’s words: the study indicates “the potential for microbial growth and metals leaching in untreated condensate collections, emphasizing the need to manage these systems similarly to other premise water distribution systems during reuse.” EPA says the conclusions are consistent with existing guidance and will support code language for condensate collection and use. A poster summarizes the microbiology and metals results, including how Legionella and other opportunistic pathogens can be controlled. A peer-reviewed journal article is in preparation, so the summary does not publish the measured concentrations.

The same summary gives the scale that makes condensate worth studying: “In humid zones, a 100,000 square foot building (or if arid, a 200,000 square foot building) can produce one million gallons of A/C condensate per year.”

What the older guidance already said

EPA’s WaterSense at Work guide reached a similar position years earlier. It says condensate “is generally safe without additional treatment for direct use in cooling towers with biocide control, or for subsurface irrigation,” but that it “can grow bacteria removed from the air in the building.” Where people “can inhale it or come into direct contact with it (e.g., spray irrigation), it should first be filtered and disinfected.” The same guide recommends disinfection “for all water used indoors for toilet flushing or other uses.”

One gap remains open. An EPA-led modeling study of onsite reuse noted in 2021 that “specific LRTs have not been defined for condensate” (Arden and others, Water Research, 2021). LRTs, or log reduction targets, are the pathogen reductions a treatment train must achieve for a given use. Until targets exist for condensate, designers borrow those set for roof runoff and rely on monitoring.

So the answer to “is it safe” is conditional. For a cooling tower with a working biocide program, or for drip lines under mulch, federal guidance treats condensate as usable with little or no added treatment. For anything that sprays, splashes or sits in a tank inside the building, it needs filtration, disinfection and monitoring like any other building water system.

How much condensate a building makes

A large building makes somewhere between a few hundred and a few thousand gallons of condensate on a humid day, depending on its floor area, how much outdoor air its units bring in and how many hours they run. The published rules of thumb disagree by several times. The number worth planning on comes from measuring your own air handlers.

EPA’s WaterSense at Work guide gives the range most planners start with: “three to 10 gallons per day per 1,000 square feet of air conditioned space, depending on the type of building and air conditioning system.” It says the amount depends on “the cooling load, relative humidity, and make-up air volumes.” The site’s condensate calculator uses that range.

Other estimates work per ton of cooling capacity. The SAWS manual cites an estimate for large San Antonio buildings in summer of “0.1 to 0.3 gallons per hour (gph) of water per ton of cooling or a peak rate of 0.5 to 0.6 gph per 1,000 square feet of cooled area.” SAWS itself uses 0.2 gallons per hour per ton as a nominal figure when it calculates condensate rebates. The manual also cites a published estimate of 8 gallons per ton for each day with a dew point above 60°F.

EPA’s 2026 figure sets a higher ceiling. One million gallons a year from 100,000 square feet is about 2,740 gallons a day spread over 365 days, or about 27 gallons per 1,000 square feet: well above the WaterSense range.

Rule of thumbWhere it comes fromWhat it assumesHypothetical 100,000 sq ft building with 250 tons
3 to 10 gallons per day per 1,000 sq ftEPA WaterSense at WorkTypical commercial buildings, by floor area300 to 1,000 gallons a day
0.1 to 0.3 gallons per hour per tonSAWS manual, citing a 2005 ASHRAE Journal estimateLarge San Antonio buildings, June to August600 to 1,800 gallons a day if units run 24 hours
0.2 gallons per hour per tonSAWS nominal rebate figureAnnual rebate estimates1,200 gallons a day at 24 hours
0.5 to 0.6 gallons per hour per 1,000 sq ftSAWS manualPeak summer rate1,200 to 1,440 gallons a day at 24 hours
8 gallons per ton per dayEstimate cited in the SAWS manualDays with a dew point above 60°F2,000 gallons a day
1,000,000 gallons a year per 100,000 sq ftEPA WRAP Action 4.5 (2026)Humid climate zone, a full yearAbout 2,740 gallons a day averaged over 365 days
Example (hypothetical) building of 100,000 square feet with 250 tons of cooling, for illustration only; our arithmetic. Sources: EPA WaterSense at Work, Section 8; San Antonio Water System, Condensate Collection and Use Manual (2013); EPA WRAP Action 4.5 summary (July 2026); all checked November 2026.

Why the estimates disagree

The main reason is outdoor air. A coil that cools recirculated indoor air removes only the moisture that people and processes add, while a coil that cools humid outdoor air removes far more. The SAWS manual’s worked example is a 154,440-square-foot university building with 727 tons of cooling and 100 percent outdoor air. Its measured summer condensate fell inside the per-ton range of 73 to 218 gallons an hour, roughly 11 to 34 gallons a day per 1,000 square feet by our arithmetic. The manual says the floor-area estimates were “expectably low” for a building that needs higher-than-usual cooling capacity per square foot.

FEMP’s Alternative Water Supply Tool lists the other site variables: the size of the cooling system, and its “hours of operation and temperature set points.” The season matters too: the SAWS per-ton figures describe June through August, while the EPA annual figure counts every month. A daily number means little until you attach the number of days to it.

The EPA-led 2021 modeling study shows the ceiling. Across its simulated buildings and locations, condensate systems could supply between 0 and 23 percent of total non-potable demand; rainfall and condensation satisfy only “a fraction of the non-potable demand typical of large buildings even under favorable climate conditions.” Condensate supplements city water; it does not replace it.

Jackson’s cooling season in numbers

Jackson’s climate is why condensate deserves a look here. NOAA’s 1991 to 2020 normals for Jackson International Airport put the normal daily high at 92.1°F in July and 92.2°F in August, with 2,402 cooling degree days a year, a standard NOAA measure of how much cooling the weather calls for (NOAA NCEI monthly normals). Adding up the monthly normals, about 2,111 of those cooling degree days, or 88 percent, fall from May through September.

Humidity matters as much as heat, because a coil only condenses the moisture the air carries. Averaging NOAA’s hourly dew point normals by month gives about 69°F in June, 71°F in both July and August, and 65°F in September, against 37°F in January (NOAA NCEI hourly normals). On NOAA’s normal calendar, the daily mean dew point stays above 60°F on 145 days, from May 9 through September 30, and above 55°F on 176 days, from April 23 through October 15.

The condensate calculator’s default of 180 days with steady cooling is a planning assumption, and these counts suggest it is in the right range for Jackson. Long operating hours or a lot of outdoor air add days; short office hours remove them.

Jackson's humid season: normal dew point by month Mean dew point, °F, from NOAA hourly normals 1991 to 2020, Jackson International Airport 75°F 60°F 45°F 30°F May to September: above 60°F 37.440.345.853.561.968.671.470.665.255.145.540.3 JanFebMarAprMayJunJulAugSepOctNovDec CDD 4.59.032.691.2258.1439.4531.6522.2359.8125.519.88.7 CDD row: normal cooling degree days per month, 2,402 a year. Dashed line: 60°F dew point.
Source: NOAA NCEI 1991 to 2020 normals for Jackson International Airport (station USW00003940): monthly cooling degree days, and hourly dew point normals averaged by month (our arithmetic), checked November 2026.

Measure one air handler before you size anything

The condensate calculator’s own note says to “measure one air handler with a container and a timer on a humid afternoon before you size a tank.” A simple field check takes an hour:

  1. Pick a humid afternoon with the unit at or near full load, and write down the outdoor temperature, humidity and time.
  2. Find where the condensate line discharges (an open drain, a floor sink or an outside outlet) and confirm it carries only that unit’s water.
  3. Catch the flow in a graduated bucket for a timed period long enough to collect at least a gallon.
  4. Convert the result to gallons per hour, and note the unit’s tonnage and outdoor air setting from the nameplate or the controls.
  5. Repeat on a morning, a late evening and once in a drier month to see the range.
  6. Multiply by operating hours and compare with the calculator’s low, high and midpoint for the floor area that unit serves.

For a larger project, a flow meter on the condensate line for one cooling season replaces estimates with data. That is the logic of a pilot system: one air handler, measured, with a keep, resize or remove decision at the end.

Example (fictional). The condensate calculator’s default example is the fictional Pearlbank Hotel’s air handlers serving 50,000 square feet of lobby, corridors and meeting rooms. At EPA’s 3 to 10 gallons per day per 1,000 square feet, the calculator shows 150 gallons on a cooling day at the low end, 500 at the high end and 325 as the planning midpoint, or 27,000 to 90,000 gallons over 180 cooling days. The midpoint could supply about 254 flushes of a 1.28-gallon toilet per cooling day. All figures are planning assumptions for a fictional hotel.

Which uses fit condensate, and how much treatment each needs

The best uses for condensate need a lot of water in hot weather and tolerate low-mineral water: cooling tower make-up first, then subsurface or drip irrigation. Toilet flushing and spray irrigation can work, but they bring storage, disinfection and more monitoring. Drinking, cooking, ice and bathing are never on the list.

This approach is called fit for purpose: treat the water as much as the use requires and no more. FEMP separates “restricted urban reuse,” where public exposure is limited, from “unrestricted urban reuse,” where people are likely to contact the water and “additional treatment” is required. EPA’s treatment table lists the typical needs for air handling condensate: filtration not likely needed, sedimentation not likely needed, disinfection likely needed, biological treatment not likely needed, and “segregate coil cleaning water.”

UseWho could be exposedTreatment the sources describeStorage
Cooling tower make-upWorkers near the tower; drift carries aerosolsNone added "for direct use in cooling towers with biocide control" (EPA); the tower's water treatment program must account for it (CDC)Little or none if piped straight to the basin (SAWS)
Subsurface or drip irrigationLow; water stays in the soil"Generally safe without additional treatment" (EPA); a fine filter protects emitters; watch metals and pH (SAWS)A tank if watering runs at other hours
Spray irrigationPeople can touch or inhale it"Filtered and disinfected" first (EPA); above-ground use needs the code official's approval in codes SAWS reviewedTank
Toilet and urinal flushingSplash and aerosol in restroomsDisinfection recommended for all indoor use (EPA); purple-labeled piping and backflow protection (FEMP)Tank with city make-up
Decorative fountainsPassers-by; sprayDisinfection; CDC's toolkit lists decorative fountains among features that call for a water management programRecirculating basin
Drinking, cooking, ice, bathingIngestion and full contactNot an option for a condensate system; non-potable water "has not been treated to standards safe for human consumption" (FEMP)Not applicable
Sources: EPA WaterSense at Work, Section 8, Tables 8-1 and 8-2; DOE FEMP, Alternative Water Treatment Levels and Best Management Practice 14; CDC Legionella toolkit worksheet; San Antonio Water System, Condensate Collection and Use Manual (2013); all checked November 2026. Local code decides what is allowed.

At home: condensate for plants

Homeowners ask a smaller version of the question: can the water from the AC line go on the garden? Applying EPA’s commercial range to a hypothetical 2,000-square-foot house gives roughly 6 to 20 gallons on a cooling day, a rough guide only, because the range was written for commercial buildings.

The same principles scale down. EPA treats subsurface irrigation as acceptable without added treatment, so let the water soak in at the base of ornamental plants rather than spraying it, and use it the same day rather than letting it sit in an open bucket where bacteria can grow. SAWS notes that metals can build up in soil over a long period where condensate runs through metal pipe, and that limestone or marble chips can raise its slightly acidic pH. Do not drink it or cook with it, and keep the condensate line clear so the unit can still drain.

Cooling tower make-up: the best match for condensate

Cooling tower make-up is the use FEMP, EPA and SAWS all rank first. The tower needs the most water on the hot, humid days when coils make the most condensate, and low-mineral water lets it run longer between blowdowns. A tower with a working treatment program can take condensate directly, with little or no storage.

FEMP’s cooling tower guidance explains the arithmetic (FEMP, Best Management Practice 10). A tower loses water through evaporation, drift and blowdown, so “Make-Up = Evaporation + Blowdown + Drift.” Blowdown is water drained off to keep dissolved solids from forming scale. The ratio of dissolved solids in the tower water to those in the make-up water is the “cycles of concentration.” FEMP says many systems run at two to four cycles, six or more may be possible, and “increasing cycles from three to six reduces cooling tower make-up water by 20% and cooling tower blowdown by 50%.”

Condensate helps on both sides of that equation. FEMP calls air handler condensate “particularly appropriate because the condensate has a low mineral content and is typically generated in greatest quantities when cooling tower loads are the highest.” SAWS adds that condensate “acts to dilute the TDS and extend the time between blowdown events, thereby saving even more water than simply replacing the potable makeup water.” Because tower water is already treated for corrosion, scale and microbes, SAWS says “no additional treatment is necessary when condensate water is added.” The manual cites estimates that condensate covers 5 to 15 percent of tower make-up in typical commercial buildings and up to 45 percent in high-ventilation buildings such as laboratories.

What the tower program has to handle

A cooling tower is also a known Legionella source, so condensate should be added with care. CDC’s cooling tower guidance says towers “release aerosolized water to the atmosphere” that can spread Legionella “over miles.” It names “sediment and biofilm, temperature, water age, and disinfectant residual” as the key factors in growth, and it advises: “Use potable water for system make-up water or ensure reclaimed or condensate sources are appropriately managed” (CDC, Controlling Legionella in Cooling Towers). CDC also recommends automated disinfectant feed, regular monitoring and high-efficiency drift eliminators.

In practice, managing a condensate make-up source means:

  • Run condensate to the tower basin by the shortest practical route, sloped to drain, so water does not sit in long runs.
  • Keep the city make-up connection and its backflow protection in place; the tower still needs city water on mild days.
  • Meter the condensate line and the city make-up line separately. FEMP recommends meters on make-up and blowdown and a log of quantities, conductivity and cycles.
  • Tell the water treatment vendor before the change, because softer make-up water shifts the chemistry the program is tuned to.
  • Send coil cleaning water to drain, never to the collection line (EPA and FEMP).
  • Check whether the air handlers ever run while the chiller and tower are idle. SAWS flags district cooling as a case where condensate is produced with nowhere to go.

Example (fictional). Tallowood Medical Offices is a fictional 120,000-square-foot clinic building with a chiller and a cooling tower, and its air handlers serve the whole floor area. The condensate calculator, at EPA’s 3 to 10 gallons per day per 1,000 square feet, gives 360 to 1,200 gallons on a cooling day, a 780-gallon midpoint, and 64,800 to 216,000 gallons over 180 cooling days. If the SAWS estimate of 5 to 15 percent of make-up holds, the tower needs several times that volume on a hot day, so all of it can be used without a storage tank. Entered in the water savings calculator at 780 gallons a day for 180 days, that is 140,400 gallons a year, about 188 CCF. If the building’s bills reach JXN Water’s top combined block (an assumption for this example), the avoided water and sewer charges are about $3,744 a year before operating cost. These are planning assumptions for a fictional building, not measured results.

Irrigation and toilet flushing: where storage and treatment come in

Irrigation and toilet flushing can use condensate, but both need a tank, because supply and demand do not arrive at the same hour or even in the same month. Storage is where condensate’s quality advantage can be lost: stored water warms, ages and grows biofilm unless it is treated, turned over and monitored.

Irrigation is the better seasonal match, because condensate and landscape watering both peak in summer. Drip irrigation suits condensate because EPA treats subsurface use as needing no added treatment; SAWS cites green building code language requiring a 0.004-inch filter or finer for irrigation, which also protects emitters. Spray irrigation near people needs filtration and disinfection first.

Toilet flushing is a year-round demand, while condensate is seasonal. From November through March, Jackson’s normal mean dew point sits between about 37°F and 46°F and cooling degree days stay under 33 a month, so coils make little condensate. A toilet-flushing system fed by condensate therefore runs on city make-up for much of the year. EPA recommends disinfection for all indoor non-potable use, and FEMP says reclaimed water pipes “must be color coded with purple tags or tape according to standards set by the American Water Works Association” and that local requirements may include backflow preventers.

Combining condensate with rainwater

Rain and condensate peak at different times in Jackson. NOAA’s monthly normals put March and April at 5.68 and 5.84 inches of rain, while September and October, the two driest months, average 3.48 and 3.80 inches. September’s normal mean dew point is still about 65°F, so condensate can cover part of the late-summer gap in a shared tank. The 2021 EPA-led study cites earlier work finding that a combined rainwater and condensate system had lower impacts than either alone and “yielded a greater and more constant water supply.”

Mixing has a cost. SAWS warns that rainwater “can carry traces of fecal matter from the rainwater collection surface,” so a mixed tank must be treated for the dirtier source. The first-flush diverter must sit upstream of where condensate enters, because “it is counterproductive to capture condensate in a first flush device.” Adding greywater raises organic content and Legionella risk further. The three sources are compared in greywater, rainwater or AC condensate, and the roof-to-tank details are in rainwater for toilet flushing.

Example (fictional). In the fictional Pearlbank Hotel’s design, condensate from air handlers serving 50,000 square feet (150 to 500 gallons a day on cooling days) joins roof rain in a tank of about 10,000 gallons that feeds drip irrigation. The 18,000-square-foot roof yields about 1,403 gallons a day on average from 57.35 inches of rain at 0.62 gallons per square foot per inch and 80 percent capture, and the tank sizing calculator’s example counts about 160 gallons of condensate a day averaged over the year. Because rain arrives in storms, storage limits the usable average to about 900 gallons a day. The drip lines run near guest paths, so the water is filtered and passes a UV unit before use, and city make-up enters through an air gap or a backflow preventer. Every number is a planning assumption for a fictional hotel; the example project walks through its first 120 days.

Controlling Legionella, metals and other risks

Legionella is the main microbial concern in condensate systems, and metals are the main chemical one. Both are controlled as in any building water system: keep water moving, keep tanks dark and clean, keep disinfectant where it is needed, and write the system into the water management program.

CDC says “an effective water management program is the primary strategy to control Legionella growth and spread.” Its worksheet asks whether a building has a cooling tower, a decorative fountain, more than 10 stories, or “multiple housing units and a centralized hot water system” (CDC, water management program worksheet). CDC gives Legionella’s favorable growth range as 77 to 113°F. Condensate leaves the coil cool, but a tank on a summer roof or in a hot mechanical room can sit inside that range.

SAWS calls Legionella “the pathogenic microorganism most likely to contaminate condensate collection systems.” Aerosols carry it into air handlers and tanks, and without treatment it “proliferates in warm water.” The manual says “the main parameter driving Legionella colonization in condensate collection system is the amount of organic material present,” which is why mixing in rainwater, and especially greywater, raises the risk. Algae can grow where sunlight reaches stored water, clog filters and harbor pathogens, so SAWS recommends opaque tanks.

Metals come from contact. EPA warns about copper after coil cleaning. FEMP says condensate “can also acquire heavy metals because of contact with cooling coils, and treatment to remove these heavy metals may be required.” SAWS says the slightly acidic water reacts especially with iron and steel. The fixes are mostly design choices: send coil cleaning water to drain, limit bare metal along the collection path where the use is sensitive, and test before choosing irrigation where metals could build up in soil.

Monitoring that fits a condensate system

The SAWS manual lists continuous checks that show treatment is working: pressure difference across filters, UV intensity for UV units, chlorine level or oxidation-reduction potential for chlorine or ozone, and turbidity “continuously if using UV treatment.” With continuous monitoring in place, it lists coliform sampling every 6 to 12 months; without it, monthly. It notes that total coliform is the more useful indicator for a condensate-only system, because condensate alone is not expected to contain fecal matter, while a tank shared with rainwater needs fecal indicators too.

Samples go to a laboratory certified for the analysis, and readings go into a maintenance log. The Legionella checklist lists reuse tanks among the places a program must cover.

Failure modes to design out

SAWS lists the most common ways onsite condensate systems fail. In short:

  1. A tank that is too small wastes condensate; one that is too large wastes money.
  2. Staff use the water freely, assuming it is all condensate, while city make-up fills the tank.
  3. Float switches, make-up valves or controls fail, so city water fills the tank and condensate overflows.
  4. Algae grows in tanks that let in light.
  5. Microbes grow anywhere from the drip pan to the point of use, most often in the pan and the tank.
  6. A clogged or leaking drain seal slows or stops condensate flow; SAWS says to check the drip pan at least every 12 months.
  7. Leaks go unnoticed without meters on supply and use.
  8. The intent is not met: replacing thirsty turf or plantings can save more water than supplying them with condensate.

Meters on condensate inflow, city make-up and each use are the common cure for items 2, 3 and 7.

What condensate is worth on a water bill

Condensate is worth the city water it replaces, valued at the rate you pay for the last gallons on your bill, minus the cost of running the system. That is the water savings calculator’s method: gallons replaced times the combined rate, minus operating cost, gives net savings; installed cost divided by net savings gives simple payback.

In Jackson, JXN Water’s court-approved rates from March 23, 2026 bill water and sewer together on metered use: “Water and sewer services are based on water meter readings” (JXN Water, Rates). The combined charge rises by block, from $7.48 per CCF (748 gallons) for the first 50 CCF a month to $19.95 per CCF above 350 CCF, about $10.00 to $26.67 per 1,000 gallons. Three details shape what condensate is worth:

  • It replaces metered water. Condensate that now runs to the sanitary drain is not metered, so redirecting it costs nothing on the sewer side, and every gallon of city make-up it displaces comes off the meter at your highest block.
  • Separate meters change the rate. JXN’s irrigation-only accounts pay a lower usage charge, $3.74 per CCF up to 50 CCF and up to $9.98 above 350 CCF, so condensate that replaces water on an irrigation meter saves less per gallon than condensate that replaces tower make-up on a combined account.
  • Evaporation credits matter. FEMP advises asking the utility whether it gives sewer credits for evaporative losses. If a tower already earns one, the avoided cost of condensate falls toward the water-only rate.

Simplicity decides the rest. The 2021 EPA-led study found that complete condensate systems for large buildings, with storage, disinfection and separate distribution, cost no more than local drinking water in fewer than 2 percent of the cases it modeled. Most were “more than 5 times more expensive than equivalent potable water on a per gallon basis.” A short gravity line to an existing tower basin avoids most of the parts that drive that cost. In the fictional Tallowood example, each $10,000 of installed cost adds about 2.7 years to the simple payback at $3,744 a year, before any operating cost.

Approvals and codes for condensate reuse in Mississippi

Mississippi has no state rule written for onsite water reuse, so a condensate project is approved locally, project by project. EPA lists 12 states with onsite non-potable reuse regulations or guidelines, and Mississippi is not among them (EPA, Onsite Non-Potable Water Reuse Resources). The plumbing and mechanical codes that a city or county has adopted, and its building official, decide what a project needs.

ICC notes that Mississippi adopts codes through the Mississippi Building Code Council and that outside the coastal counties “enforcement is voluntary but encouraged, leading to a mix of adoption levels across counties and municipalities” (ICC, Mississippi). In Jackson, “property owners or licensed contractors are responsible for obtaining required permits before beginning work and scheduling required inspections” (City of Jackson). The Mississippi State Board of Contractors’ Mechanical classification includes work to “install condensate drain from an air-conditioning unit to an existing safe waste or other approved disposal other than a direct connection to a sanitary system” (MSBOC, Classifications).

Other places show how local rules can treat condensate. The SAWS manual describes a 2006 San Antonio ordinance requiring new commercial buildings with 10 tons or more of cooling to carry condensate drain lines to a single onsite location so the water can be used, and a city plumbing code requiring both an air gap and an approved backflow device on make-up water to a reclaimed water tank. EPA’s 2026 summary says its results will support “inclusion of appropriate condensate collection and use practices in industry plumbing codes.”

Every Maredes reuse design includes a written code path memo: who approves the system, which code edition applies, backflow protection, labeling and monitoring. The federal, state and local layers are explained in is it legal to collect rainwater or reuse greywater in Mississippi. This article is general information, not legal or engineering advice; the local building official decides.

A checklist before you collect condensate

Start with what the building already has, then measure, then choose a use:

  1. List every air handler, rooftop unit and dedicated outdoor air unit, with tonnage, floor area served, outdoor air setting and operating hours.
  2. Trace each condensate line to its discharge point, and note which lines could reach a common point by gravity.
  3. Run the condensate calculator for the floor area served, then measure the largest unit on a humid afternoon.
  4. Rank the uses: cooling tower make-up, drip irrigation, then toilet flushing or spray irrigation.
  5. For a tower, read or install make-up and blowdown meters and talk to the water treatment vendor.
  6. For a tank, size it with the tank sizing calculator and plan disinfection, purple piping, make-up through an air gap or backflow preventer, and an overflow to drain.
  7. Add the system to the building’s water management program using the Legionella checklist.
  8. Price the savings with the water savings calculator at your top block rate, then ask the local building official what a permit will need.

A Maredes water review includes a reuse screen that looks at condensate alongside rain, laundry rinse water and greywater, and rainwater and condensate capture explains how those systems are designed. Hotels are a common fit, because air handlers, laundries and landscapes all run hardest in summer. More articles on reuse are collected in the water reuse section, and questions about a specific building can go through the contact page.