Reuse tank sizing calculator
Supply, demand and the days you need to bridge give a first tank size, and show how much city water makeup the system still needs.
For: Owners, managers and builders planning rainwater, condensate or greywater storage

Calculator
Every reuse system needs somewhere to hold water between the moment it is collected and the moment it is used. Too small a tank overflows good water; too large a tank holds water long enough to go stale and takes space a building may not have. This calculator gives a first tank size from three numbers and shows how much city water makeup the system will still need. It is for owners, managers and builders planning storage for rainwater, air-conditioning condensate, greywater or laundry rinse water.
The method
- Water you can use each day = the smaller of supply and demand.
- Storage = daily demand x the days of demand you want to store.
- Tank size = storage x (1 + your margin).
- Days a full tank covers demand = tank size divided by daily demand.
- Overflow or bypass = supply minus demand, when supply is larger.
- City water makeup = demand minus supply, when demand is larger.
The inputs and where to find them
- Reuse water produced per day. The daily average from the rainwater calculator, the condensate calculator averaged over the year, the greywater calculator, or a laundry study.
- Reuse water needed per day. Irrigation from an irrigation meter or controller schedule, toilet flushing from the greywater calculator, cooling tower make-up from its meter.
- Days of demand to store. This is the real design decision, and it depends on the source. EPA says untreated greywater should be used within 24 hours, so greywater and laundry rinse water get a day or less. Rainwater needs enough storage to carry the building between storms; Jackson International Airport averages 75.4 days a year with at least a tenth of an inch of rain (NOAA 1991 to 2020 normals), roughly one such day in five.
- Margin. Extra volume for sludge at the bottom, freeboard at the top and the range the level float needs. 5 percent is the example’s assumption.
The default example
Example (fictional). The Pearlbank Hotel, a fictional 96-room hotel, plans one tank for roof rain and condensate feeding drip irrigation. Supply averages 1,560 gallons a day (about 1,403 gallons of roof rain plus about 160 gallons of condensate, averaged over the year) against an irrigation demand of 1,600 gallons a day, with 6 days stored and a 5 percent margin. The calculator returns: water you can use each day (the smaller of supply and demand) 1,560 gal; storage for 6.0 days of demand 9,600 gal; tank size with your margin 10,080 gal; days a full tank covers demand with no new supply 6.3; supply beyond demand each day (overflow or bypass) 0 gal; demand the system cannot meet each day (city water makeup) 40 gal.
The tank size is the useful answer here: about 10,000 gallons, the figure the example project uses. The first row needs care. It compares yearly averages, so it is a ceiling. In the example project, a month-by-month balance puts the usable average for rain and condensate together at about 900 gallons a day, not 1,560.
Why storage limits the usable water
Rain does not arrive as 1,403 gallons every day. A 1-inch storm sends about 8,928 gallons off an 18,000-square-foot roof, which nearly fills a 10,000-gallon tank at once; a second storm before the tank drains overflows. Irrigation demand is not steady either: it peaks in hot, dry weeks, when the tank may already be empty and city water makes up the difference. Condensate helps in summer, but only on cooling days. A daily or monthly water balance, built in system design, tracks those mismatches. This calculator cannot.
Reading the result
- Overflow above zero: the source makes more than the use needs. A larger tank will not help; a second use might.
- Makeup above zero: the system needs a city water connection, through an air gap or a backflow preventer, sized for that volume.
- Many days stored: longer storage means older water. Treated water held for days needs a disinfectant residual or recirculation, and EPA recommends disinfection for all water used indoors.
Limits and next steps
Every reuse tank needs an overflow, a makeup supply with an air gap or backflow preventer, and a drain. DOE notes that reclaimed water piping is color coded with purple tags or tape according to American Water Works Association standards. Where the building has a water management program, the tank belongs in it: CDC’s program steps start by describing the building water systems and identifying where Legionella could grow, and a tank where water sits is one of those places (see the Legionella checklist).
For the whole sizing, from source to tank to end use, see rainwater and condensate capture.
Start with a water review.
Tell us about the building: what it is, who uses it, where the water comes from and what you would like to change. We reply with questions and a time to walk the building with you.