Yes, a building can flush its toilets with rainwater, and in a city that averages 57.35 inches of rain a year the supply is there. A working system has a clean roof and gutters, a first-flush diverter, an opaque covered tank sized for dry spells, a pump, filtration and disinfection for indoor use, and separate labeled piping to the toilets. City water tops up the tank through an air gap when the rain runs short, which in Jackson is most likely in September and October.
The roof is the easy part. The decisions that matter are how much first-flush water to throw away, how many days of flushing the tank should hold, and how much treatment water needs before it fills a toilet tank in a room where people breathe the spray. This article works through each one with federal guidance and Jackson’s own rainfall record.
Can you use rainwater to flush toilets?
Yes. The Department of Energy’s Federal Energy Management Program (FEMP) lists “toilet and urinal flushing” among the typical uses of harvested rainwater, alongside irrigation and cooling tower make-up. The questions are how much treatment it needs and how the building keeps it apart from drinking water.
FEMP’s rainwater harvesting technology review says “the intended end use of the harvested rainwater will determine the type of treatment equipment that the system will need.” Its alternative water guidance adds that irrigation needs minimal treatment, while “more treatment may be required for other non-potable applications such as cooling tower make-up and toilet flushing.”
The code view is lighter. ICC’s guide to the 2018 International Plumbing Code says that “typically, nonpotable rainwater is not required to be treated beyond filtration and protection from storage in direct sunlight and circulation to prevent stagnation.” EPA’s WaterSense at Work guidance sets a stricter habit for any indoor use: “Disinfection for pathogens is recommended for all water used indoors for toilet flushing or other uses.” Most building designs follow the stricter line, and local authorities can require it.
What about a single house?
The same logic applies at home, at a smaller scale and usually under the residential code. A homeowner can carry a bucket from a rain barrel to the bowl.
Plumbing a rain tank into a home’s toilets is plumbing work that local rules may require a permit for, with the same makeup and backflow questions as a larger building. This article focuses on buildings, where the toilets run all day and the tank, pump and treatment are sized for many people.
The parts of a rainwater toilet-flushing system, from roof to bowl
A rainwater flushing system has about a dozen parts, and each one has a job. FEMP’s technology review lists them, and the diagram below follows that list in the order water moves.
- Roof and gutters with screens. The catchment is the roof itself, measured flat. FEMP notes that lower-pitched roofs tend to catch more water than steep ones, and that smooth roofs shed water better than textured ones.
- First-flush diverter. It sends the first runoff of each storm, which carries dust, pollen and droppings, away from the tank. FEMP says a first-flush diverter “should be included in the system components.”
- Storage tank. The tank holds water between storms. It must keep light and mosquitoes out and has a level sensor, an overflow and a drain.
- Intake, pump and meter. A floating intake draws water from just below the surface, where it is cleanest. A pump pressurizes the line, and a flow meter with a data logger records what the system delivers.
- Filtration. A cartridge filter removes fine sediment so the disinfection stage can work.
- Disinfection. UV is the usual choice for indoor uses; some designs add a small chlorine dose to keep the pipes clean.
- Distribution. Treated rainwater runs in separate, labeled piping to toilets and urinals only.
Two more parts sit at the edges. A city water makeup line keeps toilets working when the tank runs low, and a backflow preventer or air gap keeps rainwater from ever reaching the drinking water. FEMP lists both.
What the roof adds to the water
The roof surface decides both how much water arrives and what comes with it. The Texas manual notes that smoother roofs yield more, and that clay or concrete tile and composite or asphalt shingle roofs can lose about 10 percent to texture, inefficient flow or evaporation. It describes tar and gravel and wood shingle roofs as usually suitable only for irrigation “due to leaching of compounds.”
Two details matter for toilets in particular. The manual warns that “roofs with copper flashings can cause discoloration of porcelain fixtures,” which shows up as stains in the bowl.
It also says lead must not be used as gutter solder in potable systems, because slightly acidic rain can dissolve it. A flushing system is not potable, but the same check belongs in the roof survey, along with overhanging trees, rooftop equipment that drips oil or coolant, and any roof treatment applied in the past.
Where the tank goes
The Texas manual gives practical siting rules. Tanks should sit as close to the roof drains and the toilets as possible, out of direct sunlight, and as high as practical to ease the load on the pump. The tank inlet must sit lower than the lowest downspout it serves, and overflow and drainage should be routed so they do not undermine the tank’s foundation or the building’s.
In a new building the tank can go below grade or in a mechanical room, which keeps it dark and cool. In an existing building a pad outside, next to the downspouts, may be the only space, with a short run to a pump and treatment skid indoors. FEMP adds that equipment should be in a secure location and enclosed against weather and animals.
How much rain a roof in Jackson collects, month by month
A roof in Jackson collects about 496 gallons per 1,000 square feet for each inch of rain, using EPA’s rule of thumb. Over an average year that is about 28,446 gallons per 1,000 square feet, but it arrives in storms and in a seasonal pattern.
EPA’s WaterSense at Work guidance gives the rule: about 0.62 gallons per square foot per inch of rain, with “a capture efficiency of 80 percent” because some water is lost to evaporation, splashing and first flush. FEMP’s review uses the same 0.62 factor monthly and puts typical system efficiency “between 0.75 and 0.9.” The site’s rainwater calculator uses roof area × rainfall × 0.62 × capture efficiency, the EPA method.
Jackson’s rainfall normals
The National Weather Service’s 1991 to 2020 normals for Jackson put annual precipitation at 57.35 inches. The wettest stretch runs from December through April, and the driest months are September (3.48 inches) and October (3.80 inches). NOAA’s monthly normals for Jackson International Airport also count rain days, which matter more for storage than monthly totals do.
| Month | Normal rain (inches) | Roof capture per 1,000 sq ft (gallons) | Days with 0.10 inch or more | Days with 1 inch or more |
|---|---|---|---|---|
| January | 5.42 | 2,688 | 7.4 | 1.8 |
| February | 5.10 | 2,530 | 6.6 | 1.5 |
| March | 5.68 | 2,817 | 7.0 | 2.0 |
| April | 5.84 | 2,897 | 6.1 | 1.9 |
| May | 4.36 | 2,163 | 6.0 | 1.5 |
| June | 4.43 | 2,197 | 6.9 | 1.2 |
| July | 5.02 | 2,490 | 7.5 | 1.5 |
| August | 4.69 | 2,326 | 6.4 | 1.4 |
| September | 3.48 | 1,726 | 4.6 | 1.2 |
| October | 3.80 | 1,885 | 4.7 | 1.3 |
| November | 4.40 | 2,182 | 5.6 | 1.5 |
| December | 5.13 | 2,544 | 6.6 | 1.6 |
| Year | 57.35 | 28,446 | 75.4 | 18.4 |
Roof capture uses 0.62 gallons per square foot per inch and 80 percent capture. Rain days are NOAA normals for Jackson International Airport, 1991 to 2020.
Two numbers in that table shape every design. Rain of a tenth of an inch or more falls on about 75 days a year, so the tank sits between storms most days. A storm of an inch or more comes about 18 times a year, so the big refills are occasional.
The calculator’s default example
The rainwater calculator opens with the fictional Pearlbank Hotel’s 18,000-square-foot roof, 57.35 inches of rain, 80 percent capture and a non-potable demand of 1,600 gallons a day for landscape irrigation. Its results: 8,928 gallons captured per inch of rain, 512,021 gallons in an average year, 42,668 gallons in an average month, 1,403 gallons on an average day, and 88 percent of the demand covered on average. A one-inch storm fills a tank of 8,928 gallons.
In the site’s example project, that roof feeds drip irrigation rather than toilets. Irrigation suits rain in an existing building because it needs no new piping inside. Toilets suit rain best in new construction, where a separate supply riser can go in from the start.
How much water the toilets actually need
Toilet demand is simple arithmetic: occupants × flushes per person × gallons per flush. What makes it tricky is the pattern, because an office flushes on weekdays and almost not at all on weekends, while apartments and hotels flush every day.
EPA WaterSense says labeled toilets use 1.28 gallons per flush or less, 20 percent less than the 1.6-gallon federal standard. Efficient fixtures cut the demand the tank must carry, so install them before sizing any rain system. The water use calculator estimates a building’s daily flushing from occupants and fixtures, and the bills show whether the estimate is close.
Example (fictional). The Ridgefern Building is a three-story office in Jackson with 36,000 square feet of floor space and a 12,000-square-foot flat roof draining to two internal drains. It has 300 occupants on workdays and 1.28-gallon toilets. Using a planning assumption of 3 flushes per person per workday, flushing takes 1,152 gallons a workday.
At 21 workdays a month, that is 24,192 gallons a month and about 290,304 gallons a year over 252 workdays. Spread over all 365 days, it averages about 795 gallons a day. Every number is a planning assumption for a fictional building.
The rainwater calculator with the fictional Ridgefern Building’s roof (12,000 square feet, 57.35 inches, 80 percent capture) and its 795-gallon average demand gives 5,952 gallons captured per inch of rain, 341,347 gallons in an average year and 935 gallons on an average day. It shows 100 percent of demand covered on average. That average hides the question the next section answers: what happens in a dry September week.
How the building’s calendar changes the tank
The same roof and the same toilets behave differently depending on when people are in the building. Before sizing anything, write down the demand pattern:
| Building | Flushing pattern | What it means for the tank |
|---|---|---|
| Office | Workdays only; near zero on weekends and holidays | Weekend rain refills the tank for Monday; average daily demand understates weekday use |
| School | School days only; long summer break | The tank can sit full for weeks in summer; plan to circulate, drain to irrigation or bypass, then flush lines before classes resume |
| Hotel | Every day, rising and falling with occupancy | Busy weekends draw hardest; a dry spell during a full house is the design case |
| Apartment building | Every day, mornings and evenings | The steadiest demand; storage days translate directly into dry days covered |
A school is the clearest warning. Water that sits warm and still for a summer break is the stagnation ICC’s guide asks designers to prevent, so the operating plan needs a summer mode as much as a winter one.
Sizing the tank so it carries the building through dry spells
Size the tank to carry flushing demand through the longest dry stretch you plan for, then let city water cover anything longer. A tank that is too small overflows in storms and runs dry between them; one that is too large costs more and holds water long enough to go stale.
FEMP’s technology review sets out four sizing steps:
- Estimate the monthly rainfall the roof can harvest over a typical year, using FEMP’s rainwater harvesting calculator or the site’s calculator.
- Estimate the application’s monthly demand over the same year.
- Compare the two month by month.
- Choose a tank that stores enough rain to meet demand “while not oversizing the tank.”
FEMP adds that large seasonal swings may call for a bigger tank to carry wet-month water into dry months, and that comparing weekly rainfall with weekly demand gives “a more precise picture.” The Texas Manual on Rainwater Harvesting states the goal: “Cistern capacity must be sufficient to store enough water to see the system and its users through the longest expected interval without rain.”
What the monthly balance shows
For the fictional Ridgefern Building, the roof collects more than the toilets use in ten average months. In September the average shortfall is about 3,479 gallons and in October about 1,574. August’s average surplus of 3,723 gallons would cover September only if the tank could hold it, and that is the real sizing question.
Monthly averages also hide the day-to-day pattern. September averages only 4.6 days with a tenth of an inch of rain and 1.8 days with half an inch or more. With rain days that sparse, a dry spell of two or three weeks is entirely possible, so even a large tank will sometimes run down.
Running the tank sizing calculator
The site’s tank sizing calculator multiplies daily demand by the days of storage you choose and adds a margin for sludge, freeboard and float range. Its default example, the fictional Pearlbank Hotel’s rain and condensate tank, uses 1,560 gallons of supply a day, 1,600 gallons of demand, 6 days of storage and a 5 percent margin. It returns 9,600 gallons of storage, a 10,080-gallon tank, 6.3 days of coverage and 40 gallons a day of city water makeup.
For the fictional Ridgefern Building, enter 935 gallons of average supply, 795 gallons of average demand, 12 days and 5 percent. The calculator gives 9,540 gallons of storage, a 10,017-gallon tank and 12.6 days of coverage, with about 140 gallons a day of average overflow and no average makeup. Because the 795-gallon figure spreads weekday flushing over seven days, a full tank covers about 8.7 workdays at the full 1,152-gallon rate.
A 1-inch storm puts 5,952 gallons into that tank, a little over half of it. Jackson averages about 18 such storms a year. The design question is not whether to install makeup water, because every rain system needs it, but how often the building is willing to use it.
Filling the fall gap with condensate
Jackson’s dry months are not its cool months. NOAA’s normals give September about 360 cooling degree days, compared with about 532 in July and 126 in October, so air handlers are still removing a lot of moisture when the roof collects the least.
FEMP notes that “a large amount of condensate can form on cooling coils in areas with hot, humid summers such as the southeastern United States.” Piping air handler condensate into the rain tank can cover part of the September shortfall, with the same filtration and UV downstream. The comparison of all three onsite sources is in which reuse source fits a building.
How makeup water should behave
Makeup water should keep toilets working without filling the tank with city water. The usual arrangement adds city water through an air gap only when the tank drops to a low level, and only enough to keep a reserve above the pump intake. If the makeup valve filled the whole tank, the next storm would find no room and go straight to overflow.
Why a bigger tank is not always better
FEMP warns that “an increased tank size will increase equipment cost.” ICC’s guide asks for “circulation to prevent stagnation,” and FEMP’s review notes that storing rain for dry months may need “additional treatment” to keep water quality. A tank sized for the longest drought on record holds most of its water for weeks, which works against both points. For many buildings, a target of one to two weeks of flushing demand, with city water makeup for longer dry spells, balances these points; the calculator lets you test other choices.
First flush: how much roof runoff to divert
Divert at least 10 gallons for every 1,000 square feet of roof, and more where the roof is dusty, shaded by trees or flat. The first runoff carries what settled on the roof since the last storm, and keeping it out of the tank is the cheapest treatment step you will buy.
The Texas manual explains that a roof collects “dust, leaves, blooms, twigs, insect bodies, animal feces, pesticides, and other airborne residues.” Leaf screens catch the large pieces; the first-flush diverter handles “the smaller contaminants, such as dust, pollen, and bird and rodent feces.” It gives two rules of thumb: divert “a minimum of 10 gallons for every 1,000 square feet,” and, in another passage, one to two gallons for each 100 square feet.
It is frank that no exact figure exists. The right volume depends on the number of dry days, the debris, tree overhang, the season and the roof surface. The manual adds that a sloped roof needs rain of about a tenth of an inch per hour to wash clean, and a flat or nearly flat roof about 0.18 inch per hour.
| Rule | Basis | Fictional Ridgefern roof, 12,000 sq ft |
|---|---|---|
| 10 gallons per 1,000 sq ft (minimum) | Texas manual | About 120 gallons per storm |
| 1 to 2 gallons per 100 sq ft | Texas manual | About 120 to 240 gallons per storm |
| First 2 mm of rain (about 0.08 inch) where no local data exist | Portuguese specification, as described in a 2025 Frontiers study | About 589 gallons per storm |
On a flat commercial roof, the gap between those rules is a judgment call: Ridgefern’s roof is flat, which argues for the upper end. Diverted water goes to grade, a planted area or a storm drain, never back into the tank.
Keeping the diverter working
The simplest diverter is a standpipe that fills first and drains slowly. The Texas manual notes that a 4-inch pipe holds a gallon in about 18 inches of length, so a building-scale first flush of 120 gallons or more needs a tank-style or automatic diverter rather than a length of pipe. FEMP’s maintenance table asks owners to check the diverter monthly and after prolonged storms, to make sure it is “diverting only the initial flush of water during rainfall.”
Treatment for toilet flushing: screening only, or filtration plus UV?
For toilets, use filtration plus disinfection, usually UV, and keep the tank dark, covered and circulating. Screening alone suits subsurface irrigation, not a fixture in a room where people breathe the spray from a flush.
Forum threads on this question often end without an answer because two true statements collide. Roof rain is clean compared with other onsite sources. EPA’s table of water quality concerns rates rainwater “Low” for total dissolved solids, hardness, organic load and pathogens, and says it “may be used for irrigation without additional treatment.” But a roof also collects bird and animal droppings, and toilets are indoors.
The Water Research Foundation’s 2020 guidance manual, which EPA lists among its key onsite reuse resources, settles it by exposure. For roof runoff used indoors, it sets a 3.5-log reduction target for enteric bacteria (99.97 percent).
Its example roof runoff train meets that with a single UV reactor designed for 80 millijoules per square centimeter. It notes that a jurisdiction may add turbidity limits, which would require a turbidity meter ahead of the UV.
| End use | Who is exposed and how | Treatment to plan for |
|---|---|---|
| Subsurface or drip irrigation | Little contact | Screens and first flush; sediment filter to protect emitters |
| Spray irrigation | People near the spray | Filtration and disinfection |
| Cooling tower make-up | Aerosol from the tower | Filtration; disinfection under the tower’s water treatment program |
| Toilet and urinal flushing | Spray from each flush, indoors | Filtration plus UV, often with a small chlorine residual |
What the tank does for water quality
The tank is part of the treatment. ICC’s guide calls for “protection from storage in direct sunlight.” The Texas manual says tanks “must be opaque, either upon purchase or painted later, to inhibit algae growth,” must be covered, and must have vents screened “to discourage mosquito breeding.” FEMP’s example system uses green, FDA-approved food-grade polyester resin tanks, which it says help reduce bacterial growth, and asks designers to prevent mosquito breeding around the system.
Where water leaves the tank matters too. The Texas manual describes a floating intake that draws water from 10 to 16 inches below the surface, where it is “cleaner and fresher” than water near the bottom. Sediment settles to the floor and floating debris stays on top.
A typical treatment train
For potable rain systems the Texas manual reports that the most popular arrangement in Texas is a 5-micron cartridge filter, then a 3-micron activated carbon cartridge, then UV. A toilet-flushing system does not need to reach drinking water quality, but the same order makes sense: remove particles first so the UV lamp can see through the water. FEMP’s potable maintenance table notes that a UV lamp “typically lasts about 1 year” and loses effectiveness as it ages.
Keeping rainwater out of the drinking water
The makeup line is the one place where the rain system touches drinking water, so it gets the strongest protection. A physical air gap is best; where a physical connection is unavoidable, a reduced pressure principle backflow assembly is the usual device.
ICC’s code essentials for the 2018 code name the exact case: “a bypass connection from the potable water system to a nonpotable rainwater system as makeup water” must be protected under the code’s backflow section. It calls a physical air gap “the best protection” and a reduced pressure principle assembly “the appropriate method” where a physical connection is necessary. Storage tanks must be identified as nonpotable, and outlets and piping are signed and labeled.
FEMP’s maintenance table asks for the backflow preventer to be tested by “an approved professional” annually or as often as local rules require. Its alternative water guidance adds that reclaimed water pipes “must be color coded with purple tags or tape according to standards set by the American Water Works Association,” with signs at valves, meters and fixtures.
In practice, a rainwater flushing system should have purple pipe or tape on every treated line and a “non-potable” label on the tank. It also needs signs at the fixtures it serves and as-built drawings that show which riser is which. Rainwater should never connect to a sink, shower, drinking fountain or ice machine.
Maintenance: what the building signs up for
A rainwater system needs weekly attention at the roof, monthly checks of the moving parts and an annual backflow test. FEMP’s technology review gives a component-by-component schedule.
| Component | Task | Suggested frequency |
|---|---|---|
| Roof and gutters | Keep clear of debris, especially after dry spells and storms | Weekly |
| Inlet filter or screen | Clean; replace on the maker’s schedule | Weekly |
| First-flush diverter | Clean; confirm it diverts only the initial flush | Monthly and after prolonged storms |
| Storage tank | Inspect for cracks and leaks; blow down sediment if needed | Annually |
| Overflow | Check it is clear | Monthly |
| Controls and level indicator | Confirm they respond as intended | Monthly |
| Treatment system | Clean and replace filters; check dosing | Maker’s intervals |
| Pump | Check motor, vibration, noise and temperature | Monthly |
| Backflow preventer | Test by an approved professional | Annually, or as local rules require |
| Flow meter | Calibrate; log readings | Monthly |
| Makeup connection | Inspect connection and backflow device | Annually |
FEMP expects little sediment in a well-screened tank: “2 mm to 2 in. per year.” It notes that manufacturers often warrant tanks and pipework for 15 to 30 years and pumps for 2 to 10 years.
What tends to fail
The pump is the usual weak point. The UK Environment Agency report cites a 2001 BSRIA review of maintenance logs that found the pump “the most likely point of failure in a rainwater system, often due to fouling by debris or because of electrical issues.” Most of the systems that review covered needed more maintenance than guidance documents suggested, partly to correct faults likely related to installation.
The same report reproduces the British standard’s default schedule for when a maker gives none: annual checks of gutters, filters, the tank, pumps, the backup supply and its air gap, controls and alarms, wiring, pipework and markings, a full drain-down and tank clean every 10 years, and UV lamps cleaned or replaced every 6 months. Two failures deserve their own alarm in a flushing system: a makeup valve stuck open, which hides itself because toilets keep working, and a UV lamp that has failed or passed its rated life.
Testing the water
Sampling requirements for an indoor rain system come from the local authority, so ask before start-up. A sensible baseline is a sample before and after treatment once the system is running, repeated after any repair or long shutdown. The Texas manual makes the same before-and-after point for drinking water systems, “to ensure treatment is working.”
Practical details trip people up. The manual notes that bacteria samples usually need a sterile container issued by the laboratory and must reach it within a set time, 30 to 36 hours in its Texas example. Arrange the laboratory, the containers and the courier before the sampling day, and use a laboratory certified for the tests you need.
Energy is mostly pumping
A rain system’s running cost is mainly electricity for the pump, plus the UV lamp. The UK Environment Agency’s 2010 report found reported operating energy of about 0.6 to 5 kilowatt-hours per cubic meter for rainwater systems, rising to 7.1 with UV. For a typical rainwater application, it put operational energy and carbon about 40 percent above UK mains water.
Pump selection and controls drive most of that, so a variable-speed or right-sized pump is worth specifying.
Permits and approval in Mississippi
Rainwater collection is not regulated by the federal government, and indoor use is governed by the plumbing code your local jurisdiction applies. Plan for a plumbing permit and an early conversation with the building official.
FEMP states that “rainwater harvesting is not regulated by the federal government” and that individual states regulate collection and use. It adds that rainwater harvesting permits “may be required” and advises planning for them early. ICC’s guide is blunt about indoor systems: even when the code addresses them, “they may not be approved for use locally.”
This is general information, not legal advice; local rules apply. For the Mississippi layers in detail, read whether rainwater collection and greywater reuse are legal in Mississippi. For the code requirements inside the building, see what the plumbing code requires for reuse systems.
A planning sequence for a rainwater flushing system
Most of the decision can be made with a roof plan, a year of water bills and an afternoon with the calculators. Work in this order.
- Measure the catchment. Use the flat, plan-view area of the roof sections that drain to one point, and note trees, rooftop equipment and the roof surface.
- Estimate supply. Run the rainwater calculator with your roof and your location’s rainfall normal, then build a month-by-month table like the one above.
- Estimate demand. Count occupants, flushes and gallons per flush, separate weekdays from weekends, and check the result against the bills. Replace inefficient toilets first.
- Pick the storage target. Decide how many days of flushing the tank should carry, then size it with the tank sizing calculator, keeping the tank dark, covered and circulating.
- Set the first flush. Start at 10 gallons per 1,000 square feet and go higher for flat, dusty or shaded roofs.
- Choose treatment for the use. For toilets, plan on filtration and UV and ask the local official what residual and testing they expect.
- Protect the drinking water. Bring makeup water in through an air gap, label every pipe and tank, and schedule the annual backflow test.
- Plan the upkeep. Assign the weekly, monthly and annual tasks to a named person before the system is built.
If your building pairs a large roof with steady flushing demand, the rainwater and condensate capture service describes how Maredes, a Jackson, Mississippi company that designs compact water treatment and reuse systems for one building at a time, approaches these systems. The system design service covers drawings, equipment specifications and the code path memo.
To compare rain with greywater and air-conditioning condensate, read which reuse source fits a building. More reuse articles are in the water reuse section, and you can describe your building to start with a water review.