To reduce water use in a hotel, work in this order: read the meter and set a baseline per occupied room-night, fix leaks, replace guest room fixtures, tighten laundry practice and equipment, then the kitchen, ice machines, cooling and irrigation. Water reuse comes last, sized to whatever demand is left. The order follows cost and dependency: leaks and fixtures usually cost the least to fix, and every gallon you stop wasting is a gallon a reuse system no longer has to collect, treat and store.
The stakes are large. EPA WaterSense says hotels and other lodging account for about 15 percent of all water used in commercial and institutional facilities in the United States. Its hotel fact sheet names restrooms, laundry, landscaping, kitchens, and heating and cooling as the largest uses. This article turns those agency tip sheets into an order of work, with the published result behind each step and the extra weight that cooling and irrigation carry in a humid Southern climate.
The order of work at a glance
The short version is a ladder. The lower rungs usually cost the least, and each one changes the numbers for the rungs after it.
| Order | Measure | What a published source reports | Why it sits here |
|---|---|---|---|
| 1 | Meter readings and a baseline | WaterSense: “you can’t manage what you don’t measure” | Costs almost nothing, and every later result is measured against it |
| 2 | Leaks | A toilet with a stuck fill valve can run about 4,300 gallons a day (EPA) | The cheapest gallons in the building |
| 3 | Guest room fixtures | A 397-room San Antonio hotel went from about 202 to 132 gallons per occupied room per day (EPA) | Restrooms are the largest end use, about 30 percent |
| 4 | Laundry practice and equipment | Towel and linen reuse can cut loads washed by 17 percent (EPA) | Laundry is about 16 percent of hotel water |
| 5 | Kitchen and ice | One efficient pre-rinse spray valve can save a typical commercial kitchen more than 7,000 gallons a year (EPA) | About 14 percent, plus ice machines in the corridors |
| 6 | Cooling and irrigation | Doubling cooling tower cycles from three to six cuts make-up water by 20 percent (EPA) | About 28 percent combined nationally, often more in the South |
| 7 | Reuse | Simple laundry rinse recycling saves 10 to 35 percent of laundry water (EPA) | Sized to the demand that remains after steps 1 to 6 |
The percentages in the last column come from EPA’s national end-use shares for hotels, explained in the next section. A property with an on-premise laundry, a pool or a cooling tower can look quite different, which is exactly why step 1 is measurement.
Where EPA’s H2Otel Challenge fits
EPA launched the WaterSense H2Otel Challenge in 2014 around three verbs: assess water use and savings opportunities, change products or processes, and track progress. EPA says more than 860 hotels signed up. The formal challenge is no longer active, but EPA keeps the resources online, including the WaterUSE tool and water assessment worksheets for prioritizing projects.
The ladder above follows the same assess, change and track pattern. It also leaves a paper trail: monthly meter readings, use per occupied room-night and a dated list of measures. If your brand or a certification program asks for water records, what each scheme requires and which measures count is covered in hotel sustainability certifications.
Where a hotel’s water goes before you change anything
EPA’s fact sheet Saving Water in Hotels (March 2016) splits hotel water use into seven end uses. Domestic and restroom use leads at 30 percent. Laundry and landscaping follow at 16 percent each, kitchen and dishwashing at 14 percent, cooling and heating at 12 percent, other uses at 12 percent and pools at 1 percent.
These are national averages built from older studies. The fact sheet credits data from the New Mexico Office of the State Engineer, the American Water Works Association, its research foundation and East Bay Municipal Utility District. Treat them as a starting point for questions, not as your building’s numbers.
Why Southern hotels often look different
Two of EPA’s categories grow in a hot, humid climate. Cooling and heating covers cooling towers and other mechanical equipment, and the load on them follows the weather. NOAA’s 1991 to 2020 normals for Jackson International Airport show about 2,402 cooling degree days a year and a July mean temperature of 82.1 F.
Landscaping is the other. Long growing seasons mean long irrigation seasons, and a controller set in May can run unchanged through a wet October. Jackson averages 57.35 inches of rain a year, so a property that irrigates on a fixed timer is often watering grounds that rain has already watered.
The practical point is simple. A Mississippi hotel with a cooling tower and large lawns should expect cooling and irrigation to take a bigger share than EPA’s national pie, and should plan its review around them.
Step 1: read the meter and set a baseline per occupied room-night
A baseline per occupied room-night is the single number that tells you whether anything you do later is working. It is your total water use divided by the rooms you actually sold, so a busy month and a slow month can be compared fairly.
EPA’s WaterSense at Work guidance on metering puts the rule plainly: you can’t manage what you don’t measure. The New York City Department of Environmental Protection’s hotel manager’s guide gives the same first steps: collect historic water bills, count the water-using fixtures and appliances, observe how housekeeping, laundry and food service use water, and add occupancy data.
How to build the baseline
- Pull at least twelve months of water and sewer bills. Note the units: many utilities bill in CCF, and one CCF is 748 gallons.
- Pull occupied room-nights for the same months from the property management system.
- Divide gallons by occupied room-nights for each month. Plot the twelve results.
- Mark the months that do not fit. A summer spike may be irrigation or a cooling tower; a flat line through a slow season may be a leak.
- List every meter on the property: the main meter, any irrigation meter, and any submeters on the laundry, the cooling tower or the pool.
Example (fictional). The Pearlbank Hotel, a fictional 96-room select-service hotel, runs at 70 percent average occupancy, about 2,043 occupied room-nights a month. Its bills show about 300,000 gallons a month (about 401 CCF), or 10,000 gallons on an average day. That works out to about 147 gallons per occupied room-night. Applying EPA’s shares gives a first split of the average day: guest rooms and restrooms 3,000 gallons, laundry 1,600, landscaping 1,600, kitchen 1,400, cooling and heating 1,200 and other uses 1,200. These are planning assumptions, not measurements.
The where hotel water goes tool repeats this arithmetic for your own rooms, occupancy and monthly gallons. It deliberately uses no national gallons-per-room benchmark, because none in our sources is current and verified. Compare your hotel with its own past years instead.
Published baselines give a sense of scale
EPA’s hotel profiles report per-room figures before and after work. The Holiday Inn San Antonio International Airport used about 202 gallons per occupied room per day before a fixture retrofit and 132 after. The Hilton Palacio del Rio went from 209 to 107 gallons per room between 2004 and 2011. Both are single properties in one city, so read them as examples of change, not as targets.
Ask about submeters and sewer credits
WaterSense notes that submeters on specific uses, such as a cooling tower or landscape irrigation, show where water goes and can reveal leaks and malfunctioning equipment. It also notes that most utilities bill sewer from the water meter, which assumes every gallon that enters leaves through the sewer. Irrigation water and water evaporated from a cooling tower do not. Some utilities offer a sewer credit through a deduct meter, so ask yours whether it does and what metering it requires.
Step 2: find and fix leaks before buying anything
Leaks come first because a repaired leak saves water at almost no capital cost, and a leak left running will distort every measurement that follows. EPA’s leak detection guidance puts numbers on common failures.
| Failure | Leak rate | Water lost | Cost at $26.67 per 1,000 gallons |
|---|---|---|---|
| Toilet, worn flapper | 0.02 gpm | about 860 gallons a month | about $23 a month |
| Toilet, misaligned flapper | 0.2 gpm | about 8,600 gallons a month | about $229 a month |
| Toilet, stuck fill valve | 3.0 gpm | about 4,300 gallons a day | about $3,440 a month |
| Drip irrigation malfunction | 1.0 gpm | about 43,200 gallons a month | about $1,152 a month |
| Stuck float valve in a cooling tower | 5.0 gpm | about 216,000 gallons a month | about $5,761 a month |
Leak rates and volumes are from EPA WaterSense at Work, Section 2.2 (November 2023). The cost column is our arithmetic at an example combined water and sewer rate of $26.67 per 1,000 gallons, which is JXN Water’s block above 350 CCF a month from March 23, 2026, the block a mid-size hotel’s last gallons often fall in. A separate irrigation-only account has its own rates, half the combined rates on JXN Water’s rate page, so the irrigation row would cost less on such a meter.
Four leak checks that fit a hotel
- The night meter test. WaterSense suggests reading the meter during off-peak hours with all water uses shut off, then reading it again an hour later. In a hotel, nothing is ever fully off, so do it in the small hours and compare with the same window on other nights.
- Toilet dye tests. EPA’s Fix a Leak Week guidance is a few drops of food coloring in the tank: if color shows up in the bowl after 10 minutes without a flush, the toilet leaks. Housekeeping can run this in every room on a schedule, and flush afterward so the tank does not stain.
- Tub spout diverters. In tub and shower combinations, the diverter sends water up to the showerhead. EPA’s showerhead guidance cites a study in which 34 percent of diverters assessed leaked more than 0.1 gpm, with an average leak of 0.8 gpm. For example, if a guest showers for eight minutes with a diverter leaking at that average, about 6.4 gallons of mostly hot water go straight down the tub drain.
- The cooling tower and irrigation. Check that the tower fill valve shuts off cleanly when the basin is full, and walk the irrigation zones during a scheduled run to find broken heads and wet spots.
Use interval data if your utility offers it
A monthly bill tells you a leak happened weeks after it started. WaterSense’s leak guidance suggests asking the utility whether the meter is part of advanced metering infrastructure, which records use at least hourly, and whether a customer portal or high-use alert is available. If not, read the meter and the bill every month and compare each month with the previous one and with the same month last year, allowing for summer cooling and irrigation.
A cheaper middle step is a submeter you read yourself. WaterSense names cooling tower make-up lines and irrigation systems as typical places to put one, and a weekly reading in a log turns a silent failure into a visible jump.
NYC DEP’s guide adds a reminder for pools: a leak the size of a pinhole can lose 30,000 gallons in a month. The two running toilets in the fictional Pearlbank review were found exactly this way, and hotel staff fixed them before any design began.
Leak detection in buildings where hundreds of toilets share one meter is its own subject. For sensors versus periodic checks and the repair workflow, see the hotels and apartments section of this journal.
Step 3: replace guest room fixtures
Guest room fixtures come next because restrooms are the largest end use and modern fixtures are proven. WaterSense labeled toilets, showerheads and faucets are independently certified to be at least 20 percent more water-efficient than standard models and to perform as well or better, according to EPA’s hotel fact sheet.
The numbers that matter
| Fixture | Federal maximum | WaterSense labeled | Older units often found |
|---|---|---|---|
| Tank-type toilet | 1.6 gallons per flush | 1.28 gallons per flush or less | 3.5 to 5.0 gallons per flush |
| Showerhead | 2.5 gpm | 2.0 gpm or less | 3.0 to 5.0 gpm |
| Private-use lavatory faucet | 2.2 gpm at 60 psi | 1.5 gpm or less | 2.5 gpm at 80 psi, the limit before 1998 |
Figures are from EPA WaterSense at Work Sections 3.1, 3.3 and 3.4 (May 2023). EPA names California, Hawaii and Washington among the few states that require showerheads of 1.8 gpm or less.
What two Texas hotels reported
EPA’s profile of the Holiday Inn San Antonio International Airport describes a 1981 building with 397 guest rooms. Through the San Antonio Water System’s WaterSaver Hotel program, the utility paid about $100,000 to replace 397 toilets of 3.5 or 5.0 gallons per flush with 1.1-gallon models, 397 faucet aerators of 2.2 gpm with 1.5 gpm, and 397 showerheads of 2.5 gpm with 1.75 gpm. Water use fell 35 percent, to 132 gallons per occupied room per day.
The hotel estimated it saves about 7 million gallons and about $35,000 a year in water and sewer bills. EPA’s profile adds an estimated $33,000 a year in energy savings from reduced hot water, a payback of less than two years had the hotel paid for the work itself, and a drop in maintenance calls on these fixtures from one or two a day to none.
The Hilton Palacio del Rio, built in 1968 with 470 guest rooms, replaced 525 toilets of 5.0 gallons per flush with dual-flush models, 616 faucet aerators and 479 showerheads (2.5 to 1.5 gpm). With other measures, EPA reports savings of 26 million gallons a year, a 49 percent reduction.
Example (fictional). Suppose a 120-room hotel averages 2,500 occupied room-nights a month and replaces 2.5 gpm showerheads with 2.0 gpm WaterSense labeled models. Assume, as a planning figure, 15 minutes of showering per occupied room-night. The saving is 0.5 gpm times 15 minutes, or 7.5 gallons per occupied room-night: about 18,750 gallons a month and 225,000 a year. At an example combined rate of $26.67 per 1,000 gallons, that is about $6,000 a year in water and sewer charges, before counting the gas or electricity no longer spent heating that water. Every input here is an assumption to replace with your own counts.
Get the details right
- Check pressure first. WaterSense recommends confirming system pressure is between 20 and 80 psi so a low-flow showerhead delivers the flow and spray it was tested for.
- Check the shower valve. The same guidance says the valve should meet the ASSE 1016 temperature control standard at the flow rate of the new showerhead, to limit temperature swings and scalding risk.
- Pilot a few rooms. Put new fixtures in a handful of rooms, collect housekeeping and guest feedback for a few weeks, then roll out.
- Do not forget public restrooms. WaterSense labels urinals at 0.5 gallons per flush, and NYC DEP’s guide notes they often have room for improvement.
Housekeeping is part of the fixture plan
New fixtures only save what the people using them allow. NYC DEP’s guide points out that housekeeping can waste water by flushing toilets repeatedly and leaving showers and faucets running while cleaning, and recommends a standardized cleaning process and staff training.
The same guide lists smaller changes that add up across a property: dry powder carpet cleaning instead of steam or other wet methods, window cleaning on call rather than on a fixed schedule, and a clear way for staff to report running toilets and dripping taps. Write the leak checks from step 2 into the housekeeping room checklist, so every cleaned room is also an inspected room.
Step 4: tighten the laundry before you add equipment
Laundry is about 16 percent of hotel water nationally, and far more in a property that washes for itself and sister hotels. Start with practice, then equipment, then recycling.
Practice: loads, linens and full machines
EPA’s hotel fact sheet says towel and linen reuse programs can help reduce the loads of laundry washed by 17 percent. NYC DEP’s guide estimates that each set of towels and bed sheets takes about 6 to 8 gallons of water to launder, and warns that the program only works if housekeeping honors guest requests and guests have somewhere to hang towels to dry.
EPA’s laundry guidance adds operating rules that cost nothing:
- Run full loads, and use a laundry scale to confirm them.
- Sort by soil level, since heavily soiled items need more cycles than lightly soiled sheets.
- Preset machines to their most water-efficient cycles.
- Ask the laundry chemical supplier for programs with fewer wash and rinse steps.
- Submeter the laundry and watch the readings for leaks and drift.
Hot water is the hidden cost in every load. EPA’s laundry guidance, citing ENERGY STAR, says water heating consumes about 90 percent of the energy it takes to run a clothes washer, and notes that many newer detergents work in cold water. So a gallon saved in the laundry usually saves heating fuel as well as water and sewer charges.
Equipment: gallons per pound
Washer extractors, the machines most hotel laundries use, hold 30 to 800 pounds per load and typically use 2 to 4 gallons of water per pound, EPA says. Machines with built-in rinse recycling can use less than 2.5 gallons per pound, and tunnel washers in very large laundries use 2 gallons or less.
EPA’s profile of the Westin Riverwalk in San Antonio, a 473-room hotel, shows what equipment plus simple recycling can do. It replaced three 125-pound washers and one 55-pound washer extractor with high-efficiency models (a 45 percent cut in water use) and added a last-rinse, first-wash reclaim that reused final rinse water for the next load’s first wash. Together, laundry water fell 65 percent, from 2.82 to 0.99 gallons per pound.
At seven loads a day of 240 pounds, that was more than 2.2 million gallons a year. The hotel’s $79,000 investment was offset by $27,000 in utility rebates, and EPA reports a 2.6-year payback.
Where ozone and recycling fit
Two retrofits go further: ozone systems, which mainly cut hot water, and wash water recycling, which mainly cuts water and sewer volume. They behave very differently depending on your rates and pounds per day. The comparison, with the federal demonstrations that measured both, is in ozone laundry or laundry water recycling. For how rinse water reuse is designed for a hotel, see laundry water recycling.
Step 5: the kitchen, ice machines and the pool
Kitchens are about 14 percent of hotel water in EPA’s split, and the fixes are well documented and mostly cheap. Ice machines and pools sit outside the kitchen but belong in the same pass.
Kitchen
- Pre-rinse spray valves. EPA’s hotel fact sheet says replacing one with a WaterSense labeled model can save a typical commercial kitchen more than 7,000 gallons a year. NYC DEP notes older valves may use 2 to 5 gpm, against 1.28 gpm for labeled models.
- ENERGY STAR equipment. The same fact sheet says ENERGY STAR certified dishwashers, ice machines, steam cookers and combination ovens can reduce water and energy use by at least 10 percent.
- Continuous flows. EPA suggests replacing or turning off equipment that runs water constantly, such as dipper wells.
- Steamers. NYC DEP notes that boiler-fed food steamers use large amounts of water and that connectionless steamers or combination ovens may be worth the switch.
Ice machines
Hotels buy a lot of ice machines: NYC DEP’s guide says hotels account for over 20 percent of commercial ice machine purchases in the United States. The water question is how the machine sheds heat. EPA’s WaterSense at Work section on ice machines (February 2025) reports that water-cooled machines with single-pass cooling use 100 to 300 gallons per 100 pounds of ice, while air-cooled machines use less than 50.
Both San Antonio’s Hilton Palacio del Rio and the Hyatt Regency Atlanta replaced single-pass water-cooled ice machines with air-cooled models, 22 and 25 machines respectively, according to EPA’s profiles. NYC DEP also suggests asking whether every machine is needed.
Pool and spa
Pools are only 1 percent of hotel water in EPA’s national split, but a single pool can matter in a small property. EPA’s WaterSense at Work section on pools cites a California estimate that evaporation, filter backwashing and mineral buildup control account for 56, 23 and 21 percent of pool water use. Covers reduce evaporation, and a submeter on the pool make-up line shows leaks that would otherwise hide in the main meter.
Step 6: cooling and irrigation, the Southern loads
Cooling and irrigation are where Gulf South hotels most often differ from the national pie, and both respond to measurement and control rather than new fixtures.
Cooling towers
A cooling tower loses water to evaporation, drift and blowdown, the water drained to keep dissolved solids in check. EPA’s cooling tower guidance measures performance in cycles of concentration: how many times the water is concentrated before it is blown down. Many systems run at two to four cycles; six or more may be possible.
EPA’s arithmetic is worth memorizing: raising cycles from three to six cuts make-up water by 20 percent and blowdown by 50 percent. The guidance recommends conductivity-controlled blowdown, a log of make-up and blowdown volumes, and a water treatment vendor chosen for water efficiency. Maredes does not run chemical treatment programs for cooling towers; that stays with the tower’s treatment vendor.
The Hyatt Regency Atlanta, a 1,260-room hotel, is EPA’s Southern example. Over 15 years it raised its six towers from 5.0 to 8.0 cycles using conductivity metering and automated blowdown. It also sends about 1 million gallons a year of air handler condensate to the towers; EPA reports the $12,000 condensate recovery system paid back in six months. The hotel used 35 percent less water in 2013 than in 2000.
Count the condensate you already make
Every air handler in a humid climate already produces water and sends it down a drain. EPA’s WaterSense at Work puts condensate at 3 to 10 gallons per day per 1,000 square feet of air-conditioned space, highest when cooling loads are highest. For the fictional Pearlbank Hotel’s 50,000 square feet served by central air handlers, that is 150 to 500 gallons on a cooling day, the range the condensate calculator shows by default.
Before anyone sizes a tank, measure one unit: a bucket and a timer at a condensate drain on a humid afternoon give a real number to set against the range. Condensate is low in minerals, which suits cooling tower make-up, but EPA notes it can grow bacteria, so it is filtered and disinfected before any use people can touch or breathe.
Irrigation
EPA’s irrigation guidance (November 2023) says better irrigation mechanisms and practices could cut a property’s outdoor water use by more than 50 percent. It reports that properly installed WaterSense labeled controllers can reduce irrigation water use by 15 to 30 percent, that microirrigation uses 20 to 50 percent less water than spray sprinklers, and that pressure-regulating spray bodies can cut spray sprinkler use by more than 20 percent where pressure exceeds 60 psi.
For a hotel, the sequence is an irrigation audit by a professional certified through a WaterSense labeled program, a controller that responds to weather or soil moisture, drip in planting beds, and turf kept where guests use it. In Jackson, an irrigation-only account is billed at its own usage rates, half the combined water and sewer rates on JXN Water’s rate page, so know which meter your sprinklers are on before you price any savings.
Step 7: size reuse to what is left
Reuse is the last rung because it usually needs tanks, pumps, treatment and a permit, and because it should be sized to the demand that remains after efficiency. A tank sized to last year’s wasteful irrigation schedule will sit half empty once a weather-based controller is installed.
Hotels have four candidate sources, and in a humid climate the order usually starts with the simplest:
| Source | Typical use | What the source says | Practical note |
|---|---|---|---|
| Laundry final rinse | Next load’s first rinse | Simple recycling “rarely needs treatment” and saves 10 to 35 percent (EPA) | Small tank beside the washers; talk to the chemical vendor first |
| Air handler condensate | Cooling tower make-up, irrigation | 3 to 10 gallons per day per 1,000 square feet of air-conditioned space (EPA) | Peaks when tower demand peaks; can grow bacteria, so treat it before any use people touch |
| Roof rainwater | Irrigation, tower make-up | About 0.62 gallons per square foot per inch of rain, with 80 percent capture typical (EPA) | Arrives in storms, so storage decides the usable share |
| Greywater (showers, lavatories) | Toilet flushing | Disinfection recommended for all indoor reuse (EPA) | Needs separate drain and supply piping, which existing hotels rarely have |
The EPA figures in this table come from WaterSense at Work Sections 3.5 and 8. Reuse water is always non-potable. Drinking water, ice and guest showers stay on city or well water.
Example (fictional). After the leak fixes, the Pearlbank Hotel’s planned design pairs simple laundry rinse recycling (400 gallons a day, 25 percent of laundry water) with a rain and condensate tank of about 10,000 gallons feeding drip irrigation, about 900 gallons a day usable on average, with filtration and UV because the drip lines run near guest paths. Greywater for toilet flushing was screened and not chosen, because the building has no separate drain and supply piping. Planned result: 1,300 gallons a day of city water replaced, 13 percent of supply. The hotel uses about 401 CCF a month, so at an example combined rate of $26.67 per 1,000 gallons (JXN Water’s block above 350 CCF) that is about $12,655 a year avoided, minus an example $2,400 operating cost: about $10,255 net and a 5.9-year simple payback on an example $60,000 installed cost. Part of the saving would fall in the next block down once monthly use drops below 350 CCF, so the real figure would be slightly lower. Every figure is a planning assumption. The example project follows the hotel through its first 120 days.
Greywater looks plentiful on paper in any hotel, because guests shower every day. Whether it is worth piping is a separate question, covered with documented installations in greywater recycling in hotels. Any reuse loop also belongs inside the building’s water management program for Legionella, which the Legionella checklist helps start.
What savings are worth on a Jackson bill
Savings come off the top of the bill. Utilities that charge in rising blocks bill your last gallons at your highest rate, so cutting use saves at that block, not at the average.
JXN Water’s combined water and sewer rates from March 23, 2026, billed from the water meter, are:
| Monthly metered use | Combined rate per CCF | Per 1,000 gallons (derived) |
|---|---|---|
| 0 to 50 CCF | $7.48 | about $10.00 |
| 51 to 150 CCF | $14.96 | about $20.00 |
| 151 to 350 CCF | $17.45 | about $23.33 |
| 351 CCF and above | $19.95 | about $26.67 |
The per-1,000-gallon column divides each rate by 748 gallons per CCF. JXN Water also charges a monthly availability fee by meter size, which does not change with use. Rates change, so price every project from your current bill, not from this table.
For example, suppose a hotel uses 420 CCF in a month and cuts its use by 100 CCF. The first 70 CCF saved come out of the block above 350 CCF at $19.95 each, about $1,397. The other 30 CCF come out of the 151 to 350 CCF block at $17.45 each, about $524. The month’s saving is about $1,920, more than the same 100 CCF would be worth to a building that never left the lower blocks.
Two other values belong in the arithmetic. The first is energy: much of the water saved in showers, lavatories and laundries is hot, and EPA’s San Antonio profiles show energy savings of the same order as water and sewer savings. The second is maintenance: the Holiday Inn profile reports that fixture service calls stopped after the retrofit. The water savings calculator turns gallons a day into yearly dollars at your own block rate.
A checklist for the next 30 days
You can do most of the first three rungs without outside help. Use this list to start, and keep every reading in one log.
Week 1: measure
- Gather twelve months of water and sewer bills and occupied room-nights.
- Compute gallons per occupied room-night by month and plot it.
- Find every meter and submeter and photograph each register.
Week 2: leaks
- Run a night meter test on two or three nights.
- Dye-test every guest room toilet over a housekeeping cycle.
- Check tub spout diverters while a shower runs in a sample of rooms.
- Watch the cooling tower fill valve and walk the irrigation zones during a run.
Week 3: inventory
- Record flush volumes, showerhead and aerator flow rates in a sample of rooms.
- Note whether ice machines are air-cooled or water-cooled.
- Record laundry pounds per day, machine sizes and gallons per pound if the laundry is submetered.
- Write down the cooling tower’s cycles of concentration from the vendor’s last report.
Week 4: decide
- Rank the fixes by cost per gallon saved, cheapest first.
- Price fixture and equipment changes against your top block rate.
- Only then list reuse sources, sized to the demand that remains.
When you want a second set of eyes, a Maredes water review follows the same order, from the bills and meters to a walk from the meter to the roof, with findings listed cheapest first and a reuse screen at the end. The hotels page lists what that review looks at in a lodging property, and the water review checklist shows what to gather before anyone visits.