The reader questionWhich buildings need a Legionella water management program, who requires it, and what does it involve?

A plain glass thermometer stands upright in the water, its long stem dry above the waterline and its bulb below the surface among a few drifting bubbles.

CMS expects Medicare-certified hospitals, critical access hospitals and long-term care facilities to have water management policies that reduce the risk of Legionella. For other buildings, CDC’s toolkit says a program is needed when a building cares for sick or older people, has multiple housing units on a centralized hot water system (CDC’s examples are a hotel and a high-rise apartment complex), or has more than 10 stories, and that a cooling tower, hot tub, decorative fountain or central humidifier needs one even when the building does not. A program is a written routine: a team, a diagram of the water systems, the places Legionella could grow, limits for temperature and disinfectant, what to do when a reading misses, and records.

This article sorts out who asks for a Legionella water management program and how firmly, runs CDC’s eight worksheet questions on hotels, apartments, clinics, gyms and offices, and explains where closures, renovations and water reuse systems fit. It describes public guidance as of November 2026. It is not legal, engineering or medical advice, and local authorities decide what applies to a particular building.

Who requires a Legionella water management program, and how firmly

Among the sources checked for this article, the only federal expectation that names building types comes from CMS, for hospitals, critical access hospitals and long-term care facilities. Everything else is public health guidance, a voluntary standard, or a state or local rule that applies only where it has been adopted.

Who asks Which buildings What it says How binding
CMS, memo QSO-17-30 (June 2, 2017, revised July 6, 2018) Hospitals, critical access hospitals and long-term care; “general awareness” for all healthcare organizations Facilities “must develop and adhere to policies and procedures” that reduce Legionella growth and spread Tied to Medicare participation; facilities that cannot show measures “are at risk of citation”
ASHRAE Standard 188-2021 “Human-occupied commercial, institutional, multi-unit residential and industrial buildings”, excluding single-family homes Minimum legionellosis risk management requirements A standard written “to facilitate code and regulatory adoption”; it binds a building when a law, code or contract adopts it
CDC toolkit and worksheet Buildings and devices that answer yes to its questions Buildings and devices at increased risk “should have a WMP according to industry standards” Public health guidance
States and cities Varies by place ASHRAE’s fact sheet cites Michigan health facilities and New York cooling towers Binding where adopted

The CMS memo says it “does not impose any new expectations nor requirements” for hospitals and critical access hospitals. It clarifies expectations that already flow from CMS infection control rules (42 CFR 482.42 for hospitals, 483.80 for nursing facilities and 485.635 for critical access hospitals).

ASHRAE’s fact sheet for Standard 188-2021 lists where the standard has been picked up. Michigan requires health facilities to implement a program consistent with Standard 188-2018. New York requires owners of buildings with cooling towers to have a maintenance program and plan for each tower, developed under Standard 188-2015. The Uniform Plumbing Code has referenced the standard since 2021 and, in ASHRAE’s words, “mentions that jurisdictions can choose to adopt” it.

What about Mississippi?

The sources checked for this article did not turn up a Mississippi statute or Mississippi State Department of Health rule that requires a Legionella program in a hotel, apartment building, office or gym. That is the result of a search, not a legal opinion, and rules change. A licensed care facility should ask the agency that licenses it. Any other building should ask its local building official whether a local rule applies, and check its insurance policy, franchise standards and leases for a contractual requirement.

Why a building’s own pipes are the issue

Legionella usually arrives with the water in small numbers. It becomes a problem when it grows inside a building’s plumbing and devices and is then sprayed as a mist that people breathe in. That is why the responsibility sits with the building, not only with the water utility.

EPA’s table of National Primary Drinking Water Regulations lists Legionella with a health goal of zero and a treatment technique for public water systems, and describes it as “found naturally in water; multiplies in heating systems.” CDC’s 2017 toolkit, hosted by the New Jersey Department of Health, puts it plainly: “Even if the water entering your building is of high quality, it may contain Legionella.” Heating, storing and filtering water use up the disinfectant it arrived with, which lets a few bacteria become many.

How people get sick, and who is most at risk

CDC’s page on Legionnaires’ disease says people get sick “by breathing in mist containing Legionella bacteria”, that “in general, it isn’t spread person to person”, and that about 1 in 10 people who get Legionnaires’ disease die from complications. The CMS memo names those at higher risk: people “at least 50 years old, smokers, or those with underlying medical conditions such as chronic lung disease or immunosuppression.” It adds that Legionella “is less commonly spread by aspiration of drinking water or ice.”

What lets Legionella grow

The 2017 toolkit lists the conditions inside a building that favor growth:

  • Biofilm, the slime that coats any surface that stays wet, which protects Legionella from heat and disinfectant.
  • Scale and sediment, which use up disinfectant and give bacteria shelter.
  • Water temperature in the range where Legionella “grows best”, 77 to 108 F, though the toolkit notes it can still grow outside that range.
  • Pressure changes, which can knock biofilm loose and carry it downstream.
  • pH outside roughly 6.5 to 8.5, where disinfectants work less well.
  • Too little disinfectant to kill or inactivate the bacteria.
  • Stagnation, from dead legs left by renovations, unused fixtures and low occupancy.

It also names outside events: construction vibration, water main breaks and changes in the city’s water quality or disinfectant.

Grows best: 77 to 108 F Tap: 120 F or above, where possible Water heater: 140 F or above Jackson average July high (air): 92.1 F 50 F 70 F 90 F 110 F 130 F 150 F Where common water temperatures sit against the growth range
Sources: CDC toolkit version 1.1 (2017), growth range; EPA, Maintaining or Restoring Water Quality in Buildings with Low or No Use (2020), heater and tap temperatures; NOAA NCEI 1991 to 2020 normals, Jackson International Airport. Checked November 2026. Anti-scald rules can limit tap temperatures; local codes apply.

The toolkit adds a point that matters in the South: “In hot weather, cold water in pipes can heat up into this range.” Jackson’s average July high is 92.1 F (NOAA 1991 to 2020 normal at Jackson International Airport), so cold lines that run through warm ceilings, attics or mechanical rooms deserve a thermometer reading in summer.

What outbreak investigations found

CDC’s review of 27 land-based outbreaks from 2000 to 2014, published June 10, 2016, found that hotels and resorts were the most frequent setting (12 outbreaks, 44 percent), followed by long-term care facilities (19 percent) and hospitals (15 percent). Potable water was the most frequent source (15 outbreaks, 56 percent), then cooling towers (22 percent), hot tubs (7 percent) and decorative fountains (4 percent). Maintenance gaps that a water management program could address were described in 23 of the 27 outbreaks (85 percent).

A later CDC review of outbreak investigations from 2015 to 2019 reports that the most common program deficiency was a building that “lacked a WMP (43%)”, and that “all of the deficiencies associated with outbreaks could have been prevented.”

Run CDC’s worksheet on your building

CDC’s worksheet asks eight yes or no questions: four about the building and four about devices. A yes to any building question points to a program for the whole building’s hot and cold water. A yes to a device question points to a program for that device, even when the building itself needs none.

# CDC question (shortened) A yes points to
1 A healthcare facility where patients stay overnight, or a building that houses or treats people with chronic and acute medical problems or weakened immune systems A program for the building
2 A building that primarily houses people older than 65, like a retirement home or assisted living A program for the building
3 Multiple housing units and a centralized hot water system, “like a hotel or high-rise apartment complex” A program for the building
4 More than 10 stories, including basement levels A program for the building
5 A cooling tower A program for the device
6 A hot tub (spa) that is not drained between each use A program for the device
7 A decorative fountain A program for the device
8 A centrally installed mister, atomizer, air washer or humidifier A program for the device

The questions come from CDC’s worksheet page, dated March 15, 2024. That page says devices that can spread droplets containing Legionella “should have a WMP even if the building itself does not.” The 2017 toolkit spells out the rest of the rule: a yes to any of questions 1 to 4 means “you should have a water management program for that building’s hot and cold water distribution system,” and a no to all eight means you “should still maintain water systems according to manufacturer recommendations.”

Questions 1 to 4: the building Overnight patients, or people with serious medical problems treated? Mostly residents over 65? Units on one central hot water system? Over 10 stories? Yes to any Program for the building's hot and cold water systems No to all Questions 5 to 8: devices Cooling tower? Hot tub not drained between uses? Decorative fountain? Central mister, atomizer, air washer or humidifier? Yes to any Program for that device, even if the building needs none No to all Maintain water systems and devices as their manufacturers recommend
Source: CDC, Identify Buildings with Increased Legionella Risk (worksheet page dated March 15, 2024), and CDC toolkit version 1.1 (June 5, 2017, hosted by the New Jersey Department of Health). Checked November 2026. Single-family homes and small multifamily buildings such as duplexes are outside the toolkit's building standards.

Reading the questions for an ordinary building

A few words in the questions decide most answers.

  • “Centralized hot water system.” This is one water heater, boiler or storage tank serving many units through shared pipes, often with a recirculation loop. A garden apartment community with a small heater in each unit answers question 3 differently from a mid-rise with a boiler room.
  • “Including basement levels.” A nine-story building with two basement levels has 11 levels for question 4.
  • “Not drained between each use.” A hotel or gym hot tub that stays filled and heated for many users is a yes. A single-user tub drained after each bath is not what question 6 describes.
  • “Centrally installed.” Question 8 is about misters, atomizers, air washers and humidifiers fed from the building’s water system, not a tabletop humidifier.

CDC’s worksheet page says the building standards in its toolkit do not apply to single-family homes or small multiple-family residences such as duplexes, even when they have the devices in questions 6 to 8. The 2017 toolkit asks owners of several buildings on one property to start with the buildings that house or treat people at higher risk.

Example (fictional). Four invented buildings run through the worksheet.

  • Quillhaven Apartments, seven stories plus one basement level, 84 units served by a boiler room and a storage tank. Question 3 is yes, so the whole building’s hot and cold water needs a program.
  • Ninebark Family Clinic, a one-story outpatient clinic with no overnight patients that treats people with diabetes and chronic lung disease every day. The second half of question 1 asks whether a building treats people with chronic and acute medical problems, so the clinic answers yes.
  • Tallowbrook Fitness Club, two stories with locker room showers and a hot tub that stays filled all day. Questions 1 to 4 are no and question 6 is yes, so the hot tub needs its own program. The showers are maintained as the manufacturers recommend, with a flushing routine for the ones that sit unused.
  • Fernmoor Inn, three stories and 64 rooms, with two water heaters serving every room through a recirculation loop, and a fountain at the entrance. Question 3 is yes, and the program covers the fountain as well.

These are invented buildings used to show how the questions apply. A real building’s answers come from its own drawings and equipment list.

What CMS expects from hospitals, nursing homes and other care settings

CMS expects Medicare and Medicare/Medicaid certified healthcare facilities “to have water management policies and procedures to reduce the risk of growth and spread of Legionella and other opportunistic pathogens in building water systems.” The memo applies to hospitals, critical access hospitals and long-term care. It says it is “also intended to provide general awareness for all healthcare organizations.”

At a minimum, the memo says each facility’s plans and documentation must show that it:

  1. Conducts a facility risk assessment to identify where Legionella and other waterborne pathogens could grow and spread in the facility water system.
  2. Develops and implements a water management program that considers the ASHRAE industry standard and the CDC toolkit.
  3. Specifies testing protocols and acceptable ranges for control measures, and documents the results of testing and the corrective actions taken when control limits are not maintained.
  4. Maintains compliance with other applicable federal, state and local requirements.

The memo also says “CMS does not require water cultures for Legionella or other opportunistic water borne pathogens” and that testing protocols are “at the discretion of the provider.” Long-term care surveyors expect a water management plan to be available for review. They “will not cite the facility based on the specific risk assessment or testing protocols in use,” but facilities “unable to demonstrate measures to minimize the risk” of Legionnaires’ disease are at risk of citation.

Care settings the memo does not name

Assisted living, memory care, dialysis centers, urgent care and physician offices are not among the three provider types the memo covers. CDC’s worksheet still reaches many of them. Question 2 covers buildings that primarily house people older than 65, and question 1 covers buildings that treat people with chronic or acute medical problems. The 2017 toolkit’s glossary defines a healthcare facility to include “inpatient or outpatient care areas.”

For healthcare buildings, the toolkit adds team members: someone who understands accreditation and licensing requirements, someone with infection prevention expertise, and a clinician with infectious disease expertise. It also asks teams to think about ice machines, because patients who have trouble swallowing may be at risk from aspiration. Maredes plans drinking water and building water systems; it does not advise on medical equipment or patient care, and it makes no claim about compliance with healthcare rules.

What ASHRAE 188 is, and what we can say about it

ASHRAE Standard 188-2021, Legionellosis: Risk Management for Building Water Systems, sets minimum requirements for managing Legionella risk in building water systems. ASHRAE says it is “written with enforceable language to facilitate code and regulatory adoption.” In other words, it is drafted so that a code, a regulator or a contract can require it.

According to ASHRAE’s fact sheet, the standard:

  • Covers “the design, construction, commissioning, operation, maintenance, repair, replacement and expansion of new and existing buildings and their associated potable and non-potable water systems and components.”
  • Applies to “human-occupied commercial, institutional, multi-unit residential and industrial buildings, excluding single-family residential buildings.”
  • Is supplemented by ASHRAE Guideline 12-2023, which gives guidance for specific types of building water systems.

Two details from the fact sheet matter for reuse and for owners. First, the scope names non-potable water systems, so a rainwater, condensate or greywater loop is part of the picture, not an exception. Second, the fact sheet says CMS’s 2017 directive “calls for health care facilities to use Standard 188 to assist in developing the water management plans.” The CMS memo itself says a facility’s program should consider “the ASHRAE industry standard and the CDC toolkit.”

The CMS memo dates the first edition: ASHRAE published Standard 188 on June 26, 2015, and “in 2016, the CDC and its partners developed a toolkit to facilitate implementation.” CDC’s 2017 toolkit cites the standard at the foot of nearly every page. The full standard is sold by ASHRAE and was not reviewed for this article, so this article describes it only as far as ASHRAE’s fact sheet and the CMS memo do. Maredes holds no ASHRAE certification and does not claim compliance with Standard 188. Our standards page lists what Maredes does and does not claim.

Hotels and inns: hot tubs, quiet floors and centralized hot water

Many hotels answer yes to CDC’s question 3 at once, since CDC’s own example of “multiple housing units and a centralized hot water system” is a hotel. Add a hot tub, a fountain or a cooling tower and the device questions apply too. Hotels and resorts were also the most frequent setting in CDC’s 2000 to 2014 outbreak review, at 12 of 27 outbreaks.

Low occupancy and closed floors

The 2017 toolkit names “reduced building occupancy, which can occur in hotels during off-peak seasons” as a cause of stagnation, along with renovations that leave dead legs. Its worked example is an eighth floor closed for renovation. The maintenance lead flushes hot and cold water daily at several rooms, including those farthest from the riser, and raises temperature and chlorine checks on that floor from weekly to daily. He logs the flushing and every reading, and reviews them with his supervisor.

The toolkit also lists “changes in water usage (e.g., high and low season for hotel)” as an event that should prompt a review of the program. A hotel that closes a wing every winter has a predictable stagnation event and can write the flushing routine before it happens.

Hot tubs, pools and fountains

The toolkit’s hot tub example starts with a daily inspection that finds a chlorine reading of zero. The tub is closed at once, the contractor replaces a failed chlorinator pump, and the start-up protocol includes cleaning, shocking and back-flushing the filter. The program is then amended to add a daily check of equipment operation and disinfectant supply.

Pools are a different case. The toolkit says swimming pools “do not usually generate hazardous conditions because they rarely reach adequate temperature for growth or generate water droplets small enough to be inhaled.” Pools and hot tubs are also governed by state and local aquatic rules. The toolkit points to CDC’s Model Aquatic Health Code for information but says it “is not a substitute for state and local regulations.”

Ice machines on guest floors

Ice machines appear on the toolkit’s list of devices that can spread Legionella “through aerosols or aspiration,” and its example building has them on floors 2, 4, 6, 8 and 10. They belong on the program’s diagram even though the main reasons to maintain them are scale and sanitation. Our article on ice machine water filters covers what a filter does and does not do for them. For what Maredes looks at in a lodging property as a whole, see hotels.

Apartments, offices, clinics and gyms

CDC’s program overview splits buildings into two groups. In some settings “the entire building needs a WMP”: hospitals and long-term care facilities, buildings that house or serve a vulnerable population, and “large buildings and those with complex water systems.” In others, “such as small buildings with simple water systems, only devices that aerosolize water may need a WMP”: cooling towers, decorative fountains, hot tubs and respiratory equipment intended for nebulization.

Building Questions most likely to apply Usual scope
Garden apartments, heater in each unit Usually none, unless there is a hot tub or fountain Device program, if any
Mid-rise or high-rise apartments, central boiler 3, and 4 above 10 stories Whole building
Office building 4 above 10 stories, 5 cooling tower, 7 lobby fountain, 8 central humidifier Device program in many low-rise offices; whole building in towers
Outpatient clinic 1, if it treats people with chronic or acute medical problems Whole building
Gym, spa or salon 6 hot tub; showers that sit unused Device program for the hot tub, plus flushing
Shop, laundromat or small office Usually none Maintain as manufacturers recommend

The table shows typical outcomes, not answers for any real building. A shop with a decorative fountain answers question 7 yes, and a two-story office with a cooling tower answers question 5 yes. Read the questions against your own equipment list.

Offices with low occupancy

An office with empty floors or a short work week has the same stagnation problem on a smaller scale. EPA’s guidance for buildings with low or no use says stagnant water “can become unsafe to drink or otherwise use” and recommends flushing the plumbing regularly while use is low. Whether or not the worksheet calls for a full program, an office with empty floors benefits from a written flushing routine and a log.

Gyms and salons

Showers and shampoo bowls spray warm water near people’s faces, which is the exposure route CDC describes. A shower that nobody uses for a week holds stagnant water in its line and head. The toolkit’s examples of where Legionella can grow include “showerheads and hoses,” “aerators” and “infrequently used equipment, including eyewash stations.” For offices, clinics, gyms, salons and shops more broadly, see small commercial buildings.

After a closure, a renovation or a main break

Stagnation and pressure changes come up again and again in CDC’s and EPA’s examples. EPA’s 2020 guidance on buildings with low or no use describes what happens: hot water temperatures fall, disinfectant residuals “drop to low levels,” and turning water back on can disturb pipe scale and release contaminants.

EPA’s recommended steps, summarized from the guidance, are:

  1. Review the plumbing layout and water use, using CDC’s toolkit.
  2. Keep the hot water system running, with the water heater “at or above 140°F per CDC guidance to prevent Legionella growth.”
  3. Flush the service line from the main to the building first.
  4. Flush cold before hot, starting nearest where water enters the building and moving to the farthest tap.
  5. Flush hot water until it reaches its maximum temperature, which “where possible” should be “at or above 120°F” at the tap.
  6. Discard ice and follow each device’s maintenance instructions.
  7. Drain and clean storage tanks and water heaters as the manufacturer instructs.
  8. Check temperature, pH and disinfectant levels at the entry and at taps after flushing. EPA says stable readings “can be a good indicator” that fresh water has reached the whole system.

EPA also suggests contacting the local health department about local requirements before reopening. For proactive disinfection or heat treatment, it notes that these procedures “should only be performed by trained professionals.”

Main breaks, repairs and boil-water notices

The toolkit’s main break example begins with taste complaints and a brownish tint at the building entry. The facility lead calls the water provider, learns of a nearby break, and flushes fixtures near the entry until the water runs clear and falls within the program’s limits. He then raises chlorine checks at the taps from weekly to daily.

In Jackson, JXN Water posts precautionary boil-water notices after repair work. Check JXN Water’s notice page and the MSDH water safety notices for current notices. A boil-water notice is about drinking water, not Legionella specifically, but the pressure change behind it is one of the toolkit’s external triggers. Our article on why boil-water notices are issued and lifted explains the testing behind them.

Reuse systems, filters and storage tanks belong inside the program

Any equipment that stores, heats or filters water is a possible control point, and that includes a water reuse system. A program that stops at the potable water heater and ignores a rainwater tank, a condensate line or a greywater loop has a hole in it.

The toolkit’s list of places Legionella can grow includes “hot and cold water storage tanks” and “water filters.” It names “recycled or reused water” among systems that “may be of concern.” In 2017 it also said: “It is not known at this time if Legionella can grow and spread in sources such as harvested rainwater or reclaimed graywater (i.e., bath, laundry).” That uncertainty is a reason to include them, not to leave them out.

EPA’s WaterSense at Work guidance on alternative water gives the practical rules:

  • Air-conditioning condensate “can grow bacteria removed from the air in the building.” If people can inhale it or touch it, as with spray irrigation, “it should first be filtered and disinfected.”
  • Condensate “is generally safe without additional treatment for direct use in cooling towers with biocide control,” which keeps condensate make-up inside the cooling tower’s own program.
  • “Disinfection for pathogens is recommended for all water used indoors for toilet flushing or other uses.”
  • Treated greywater “should always be used within 24 hours of collection” and should not be “sprayed through conventional sprinkler heads where it has the potential to be inhaled.”

ASHRAE’s scope for Standard 188 also names “non-potable water systems and components.” As our standards page describes, every Maredes reuse design includes a section for the building’s water management program team, so the tank, the treatment and the uses can be added as control points with their own readings.

Example (fictional). The Pearlbank Hotel is the invented 96-room hotel used across this site. Its planned rain and condensate tank of about 10,000 gallons feeds drip irrigation, and because the drip lines run near guest paths, the water is filtered and passes a UV unit before use. In the hotel’s program, the tank, the filter, the UV unit and the drip zones would each be a control point. The log would record the tank level and any overflow events, the filter’s pressure readings and cartridge changes, the UV unit’s status and lamp hours, and a visual check of the drip zones. City make-up water enters through an air gap or a backflow preventer. Every figure here is a planning assumption for a fictional building.

For more on condensate quality and its uses, see our article on reusing air-conditioning condensate.

What a Legionella water management program involves week to week

A program is not a binder written once. CDC’s seven steps describe a cycle that keeps running:

  1. Establish a team with the skills to develop and run the program.
  2. Describe the building water systems with a flow diagram and a written description, including where the building connects to the city supply and where hot tubs, water heaters and cooling towers are.
  3. Identify areas where Legionella could grow and spread.
  4. Decide where to apply control measures and how to monitor them. Control measures are actions such as heating or disinfecting, control limits are the acceptable values, and control points are the locations.
  5. Establish interventions when control limits are not met: corrective actions and contingency responses.
  6. Make sure the program runs as designed and works. CDC calls these verification and validation.
  7. Document and communicate all activities, and update the plan and train staff after each change.

The Legionella checklist turns those steps into items you can tick off for your own building.

What gets checked, and where

The 2017 toolkit’s examples of control measures are simple and physical: water heaters kept at appropriate temperatures, water quality measured for changes such as a drop in chlorine, decorative fountains “kept free of debris and visible biofilm,” and disinfectant in cooling towers and hot tubs “continuously maintained and regularly monitored.” It says control limits “should include a minimum and a maximum value.”

Control point What is checked Example response when out of range
Water heaters and hot storage Temperature Find the cause, restore the setting, recheck
Taps near and far from the heaters Temperature and disinfectant residual Flush, recheck, look for mixing or dead legs
Unoccupied rooms or floors Flushing done and logged Flush daily and raise monitoring frequency
Hot tub Disinfectant level, equipment operation Close the tub, repair, follow start-up protocol
Decorative fountain Debris and visible biofilm Shut off, drain, scrub, refill and check residual
Cooling tower Disinfectant level, debris, inspection Remove debris, fix the cause, check daily for a week
Reuse tank and treatment Level, filter pressure, disinfection status Bypass to city water, service, recheck

The rows are drawn from the toolkit’s examples, plus the reuse row from EPA’s guidance. The limits themselves are set by each building’s team, often with help from the equipment makers, a water treatment professional or the health department.

The toolkit recommends monitoring “at representative fixtures close to and far from the central distribution point” and says “it is not necessary to routinely monitor water conditions at every tap.” It adds that heterotrophic plate counts can help as a water quality indicator “but should not be used as a control measure.”

Verification, validation and testing for Legionella

Verification asks whether people are doing what the program says. The toolkit suggests that people should not verify their own tasks: the person who tends the hot tub checks the cooling tower log, and the reverse. Validation asks whether the program works. The toolkit says testing for Legionella itself is useful for validation and becomes more important when a building struggles to stay within limits, has a history of disease linked to its water, or is a healthcare facility with inpatients at higher risk.

Records and review

The written program should name the team and its roles, describe the building and its occupants, describe the water systems with a flow diagram, list control measures and limits, and set out how the program is verified and validated. The 2017 toolkit asks for a review “at least once per year” and after events such as persistent readings outside limits, construction, equipment changes, new treatment products, seasonal changes in use, changes in the city supply, or a case of disease. If a case of Legionnaires’ disease is suspected, it says to contact the local or state health department, notify affected people if the department asks, decontaminate if necessary, and revise the program.

Readings belong in one place. A service plan for an installed filtration or reuse system keeps a maintenance log that can feed the same record.

What to do this month

The first question, whether this building or anything in it needs a program, takes little more than the drawings and an equipment list to answer. Here is a practical order of work.

  1. Answer CDC’s eight questions for each building you own or manage, and write the answers down with the date.
  2. List every device that sprays or stores water: cooling towers, hot tubs, fountains, misters, humidifiers, ice machines, storage tanks, and any rainwater, condensate or greywater system.
  3. Name one responsible person, even if the answer is “device program only” or “maintain as manufacturers recommend.”
  4. Ask who requires what. A care facility asks its licensing agency and checks the CMS memo. Others ask the local building official and check contracts, insurance and franchise standards.
  5. Sketch the water systems: where water enters, the heaters and storage, the risers, the devices and any reuse loops.
  6. Take a first set of readings at the water heaters and at taps near and far from them, in summer and winter.
  7. Plan for quiet periods: write the flushing routine for closed floors, seasonal wings and empty offices before the next one.
  8. Keep a log and review it at least once a year, or after any renovation, outage or change in use.

If you are planning filtration or a reuse system, the design should arrive with its control points already written down for your team. Maredes is a Jackson, Mississippi company that designs water treatment and reuse systems for one building at a time, starting with a water review and a certified laboratory test. You can ask a question or request a water review. More articles on restaurants, equipment and building water are collected under commercial water.